Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53620021-01
Printed in U.S.A.
Form 62X-1SI
Pg 48
1018
7-18
Replaces: New
© Carrier Corporation 2018
SF-APS Status
sf_aps_stat
R
BV
223
Discrete Input
10017
BD
17
SP ALARM
sp_alarm
R
ALM
851
Discrete Input
10102
BD
113
Start/Stop Switch Status
ss_sw_stat
R
BV
236
Discrete Input
10030
BD
30
Sub-Cooling Command
sc_cmd
R
BV
248
Discrete Input
10038
BD
38
nvoScCmd
SNVT_switch(95)
Sub-Cooling LDB
sc_ldb
R/W
AV
556
Holding Register
40227
ADF
181
Sub-Cooling UDB
sc_udb
R/W
AV
555
Holding Register
40225
ADF
180
Supply Air Dew Point
sa_dewpoint
R
AV
268
Input Register
30075
ADF
54
nvoSaDewpoint SNVT_temp_p(105)
Supply Air Enthalpy
sa_enthalpy
R
AV
269
Input Register
30077
ADF
55
nvoSaEnthalpy
SNVT_enthalpy(153)
Time Remaining
time_remain
R
AV
104
Input Register
30001
ADF
2
Unit Stop
unit_stop
R
BV
819
10081
BD
91
nvoUnitStop
SNVT_switch(95)
W1 Enable
w1_en
R
BV
578
Discrete Input
10067
BD
67
nvoW1En
SNVT_switch(95)
WExAT FAIL
wexat_failure
R
ALM
841
Discrete Input
10096
BD
107
WExAT Status
wexat_stat
R
AV
239
Input Register
30037
ADF
35
nvoWexatStat
SNVT_temp_p(105)
WM-CS Override Time
wmcs_ovrd_time
R/W
AV
385
Holding Register
40181
ADF
145
ZAT FAIL
zat_failure
R
ALM
852
Discrete Input
10104
BD
115
ZAT From BAS
zat_bas
R/W
AV
210
Holding Register
40027
ADF
19
nviZatBas
SNVT_temp_p(105)
ZAT Ratio
zat_ratio
R/W
AV
322
40083
ADF
91
nviZatRatio
SNVT_temp_p(105)
ZAT Status
zat_stat
R
AV
209
Input Register
30011
ADF
18
nvoZatStat
SNVT_temp_p(105)
ZAT/SAT Set Point Reset
Enable
rs_sat_en
R
BV
301
Coil
20
BD
40
nvoRsSatEn
SNVT_switch(95)
Zone Set Points
clg_zat_sp_o
R/W
AV
200
Holding Register
40011
ADF
10
nviClgZatSpO
SNVT_temp_p(105)
Zone Set Points
htg_zat_sp_o
R/W
AV
201
Holding Register
40013
ADF
11
nviHtgZatSpO
SNVT_temp_p(105)
Zone Set Points
clg_zat_sp_u
R/W
AV
202
Holding Register
40015
ADF
12
nviClgZatSpU
SNVT_temp_p(105)
Zone Set Points
htg_zat_sp_u
R/W
AV
203
Holding Register
40017
ADF
13
nviHtgZatSpU
SNVT_temp_p(105)
Zone Set Points
clg_zat_sp
R
AV
204
Holding Register
40019
ADF
14
nvoClgZatSp
SNVT_temp_p(105)
Zone Set Points
htg_zat_sp
R
AV
205
Holding Register
40021
ADF
15
nvoHtgZatSp
SNVT_temp_p(105)
Table 19 — Mapping Points for Multiple Unit Styles and Types (cont)
POINT NAME
OBJECT NAME
READ
WRITE
BACNET
MODBUS
N2
LONWORKS
TYPE
OBJECT
ID
TYPE
NUMBER
TYPE ADDRESS
SNVT NAME
SNVT