92
Universal Protocol Converter (UPC)
See Fig. 45 and Table 36.
The UPC board is required to convert CCN into Modbus proto-
col. It contains the operating software that runs the ERV logi-
cally. The UPC is connected to the
Comfort
Link controller
LEN bus on the rooftop unit.
The DIP switches should be set as follows: 1=off, 2=off, 3=on,
4=on, 5=off, 6=off, 7=on, and 8=off. The address rotary
switches should be set to 01 (10’s=0 and 1’s=1).
Do not
change these settings.
USER INTERFACE
All ERV set point adjustment, service tests, and monitoring are
accomplished through the
Comfort
Link controller scrolling
marquee interface. See the
Comfort
Link Controls, Start-Up,
Operation and Troubleshooting Instructions for further details
on
Comfort
Link controller operation. The ERV EXCB board
has a LCD screen that can be used to help troubleshoot com-
munication problems. The following are examples of the text
that can be seen on the EXCB’s LCD screen.
LCD Texts
Initialize_LEN Communication
This will occur when the ERV is turned on from a power reset.
Communication Connected
This will be displayed when correct communication is estab-
lished between the RTU and ERV and within the ERV.
Comm Failure1 UPC_to_LEN_Fail
This occurs if there is a communication problem between the
UPC and
Comfort
Link MBB.
Comm Failure2 UPC_to_EXCB_Fail
This will occur if there is a communication problem between
the UPC and the EXCB.
Warning UPC TestMODE_Enabled
This will occur if the UPC was left in a factory Test mode a
BACview
1
Handheld is needed to pull the ERV out of this
mode back to normal running mode.
Fig. 45 — Universal Protocol Converter (UPC)
1. BACView is a registered trademark of Automated Logic Corporation.
Table 36 — UPC Input/Output Connections
TERMINAL NAME
DESCRIPTION
Input/Output
TYPE OF Input/Output
CONNECTION PIN
NUMBER
24VAC
Supply power to UPC
Input
24VAC
1 - 2
Port 2
UPC Modbus
both
Communication
1 - 2
Port 1a
UPC LEN
both
Communication
1 - 3
Port 1b
Not used
N/A
N/A
N/A
Rnet
BACview User Interface or
Download Connection
both
Communication
1 - 4
Local Access
both
Communication
1 - 5
Summary of Contents for /50HC 04-28
Page 69: ...69 Fig 24 Typical Control Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Page 70: ...70 Fig 25 Typical Power Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Page 71: ...71 Fig 26 Typical Control Diagram for 50HC 04 14 Units 50HC 14 shown ...
Page 72: ...72 Fig 27 Typical Power Diagram for 50HC 04 14 Units 50HC 14 Non Humidi MiZer shown ...
Page 73: ...73 Fig 28 Typical Control Diagram 48HC 17 28 Units ...
Page 74: ...74 Fig 29 Typical Control Diagram 50HC 17 28 Units ...
Page 75: ...75 Fig 30 Typical Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Page 76: ...76 Fig 31 Typical Non Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Page 89: ...89 Fig 42 Modulating ERV Wiring Schematic ...
Page 90: ...90 Fig 43 EnergyX ERV Control Box Component Layouts ...
Page 101: ...101 Fig 59 Exhaust Fan Assembly Removal Exhaust Fan Assembly ...
Page 141: ......