130
APPENDIX C — VARIABLE FREQUENCY DRIVE (VFD) (cont)
Table X — Mode — Configuration (cont)
ITEM EXPANSION
RANGE
UNITS
DEFAULT
CCN TABLE/
Sub- TABLE
CCN POINT
ENTRY
S.VFD
SUPPLY FAN VFD CONFIG
N.VLT
VFD1 Nominal Motor Volts
0 to 999
volts
230: 208/230v
1ph or 3ph
460: 460v
575: 575v
VFD1NVLT
N.AMP
VFD1 Nominal Motor Amps
0 to 999
amps
See VFD Motor
Parameters table
VFD1NAMP
N.FRQ
VFD1 Nominal Motor Freq
10 to 500
60
VFD1NFRQ
N.RPM
VFD1 Nominal Motor RPM
50 to 30000
See VFD Motor
Parameters table
VFD1NRPM
N.PWR
VFD1 Nominal Motor HPwr
0 to 500
See VFD Motor
Parameters table
VFD1NPWR
MAX.A
VFD1 Maximum Amps
0 to 999
amps
See VFD Motor
Parameters table
VFD1MAXA
M.DIR
VFD1 Motor Direction
0=FORWARD
1=REVERSE
0 VFD1MDIR
ACCL
VFD1 Acceleration Time
0 to 1800
secs
30
VFD1ACCL
DECL
VFD1 Deceleration Time
0 to 1800
secs
30
VFD1DECL
SW.FQ
VFD1 Switching Frequency
0 to 3
2
VFD1SWFQ
COOL
Cooling Configuration
COOL_CFG
N.CIR
Number of Circuits
1 or 2
1 (04- 07)
2 (08- 28)
NUM_CIRC
MRT.C
Compressor Min On Time
120 to 999
sec
180
MIN_ON
MOT.C
Compressor Min Off Time
300 to 999
sec
300
MIN_OFF
RST.C
Runtime to Reset Strikes
120 to 999
sec
300
MIN_ON_S
C.DEC
Cool Stage Decrease Time
120 to 999
sec
300
STAGEDEC
C.INC
Cool Stage Increase Time
120 to 999
sec
450
STAGEINC
FOD.C
Fan-off Delay, Mech Cool
0 to 600
sec
30 (04-05)
75 (06- 28)
COOL_FOD
ALM.N
Alert Each Strike
No/Yes
Yes
ALM_NOW
CA.LO
Circuit A Lockout Temp
0 to 100F
°F
40
0: Low ambient
or Humidimizer
FIOP
OATLCMPA
CB.LO
Circuit B Lockout Temp
0 to 100F
°F
40
0: Low ambient
or Humidimizer
FIOP
OATLCMPB
D.CMP
Diagnose Comp Safety
Disable/Enable
Enable
DIAGCOMP
MX.SA
Max Suction Change CirA
0 to 100
PSIG
4 (04-06, 17- 28)
6 (07-12)
7 (14)
MAXDSSPA
MX.SB
Max Suction Change CirB
0 to 100
PSIG
4 (04- 06, 17- 28)
6 (07-12)
7 (14)
MAXDSSPB
CS.A1
Current Sensing A1
Disable/Enable
Disable
A1_SENSE
CS.B1
Current Sensing B1
Disable/Enable
Disable
B1_SENSE
SAT
Supply Air Temperature
SA.PD
SAT Cool Demand (+) Level
0.5 to 10
^F
1
SAT_POS
SA.ND
SAT Cool Demand (-) Level
- 10 to - 0.5
^F
-1
SAT_NEG
SAT.U
Minimum SAT Upper Level
35.0 to 65.0
°F
53 (04- 14)
56 (17- 28)
SATMIN_H
SAT.L
Minimum SAT Lower Level
35.0 to 65.0
°F
42 (04- 14)
46 (17- 28)
SATMIN_L
SPT
Space Temperature
CL.PD
SPT Cool Demand (+) Level
0.5 to 5
^F
1
DEM_POS
CL.ND
SPT Cool Demand (-) Level
- 5 to - 0.5
^F
-1
DEM_NEG
C.LAG
Cool Thermal Lag Factor
0 to 5
1
COOL_LAG
SST
Low Suction Control
SST.O
Suction OK Temperature
10 to 50
°F
18
SSTOK
SST.1
Low Suction - Level 1
10 to 50
°F
20
SSTLEV1
SST.2
Low Suction - Level 2
5 to 50
°F
15
SSTLEV2
SST.3
Low Suction - Level 3
0 to 50
°F
10
SSTLEV3
CK.DL
Delay On Low SST Check
0 to 300
sec
0
SSTCKDLY
Summary of Contents for /50HC 04-28
Page 69: ...69 Fig 24 Typical Control Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Page 70: ...70 Fig 25 Typical Power Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Page 71: ...71 Fig 26 Typical Control Diagram for 50HC 04 14 Units 50HC 14 shown ...
Page 72: ...72 Fig 27 Typical Power Diagram for 50HC 04 14 Units 50HC 14 Non Humidi MiZer shown ...
Page 73: ...73 Fig 28 Typical Control Diagram 48HC 17 28 Units ...
Page 74: ...74 Fig 29 Typical Control Diagram 50HC 17 28 Units ...
Page 75: ...75 Fig 30 Typical Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Page 76: ...76 Fig 31 Typical Non Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Page 89: ...89 Fig 42 Modulating ERV Wiring Schematic ...
Page 90: ...90 Fig 43 EnergyX ERV Control Box Component Layouts ...
Page 101: ...101 Fig 59 Exhaust Fan Assembly Removal Exhaust Fan Assembly ...
Page 141: ......