37
* These can be viewed under the CCN Table OAU_CFG with a CCN device.
†These can be viewed under Configuration
→
OAU on the scrolling marquee or Navigator™ display.
Table 12 — Configurations - ERV Configurations Read from
Comfort
Link Controller
CCN POINT*
SCROLLING
MARQUEE
POINT†
EXPANDED TEXT
RANGE
UNITS
DEFAULT
FUNCTION
OAU_TYPE
OA.TY
Outdoor Air Unit Type
0=No OAU
1=FIOP EXv2
1: FIOP EXv2
Defines what kind of OAU is
installed
OAFANCRV
OA.FC
Outside Air Fan Curve
0 to 999
1: 04
2: 05-06
3: 07
4: 08-12
5: 14
6: 17-20
7: 24-28
Determine what outside air fan
curve to use
PEFANCRV
PE.FC
Exhaust Air Fan Curve
0 to 999
1: 04, 1ph, and econ
2: 04, 3ph, and econ
3: 04, 1ph, and no econ
4: 04, 3ph, and no econ
5: 05-06 1ph
6: 05-06 3ph
7: 07
8: 08-12
9: 14
10: 17-20 and econ
11: 17-20 and no econ
12: 24-28
Determine what exhaust air fan
curve to use
UNOCCRUN
U.RUN
OAU Unoccupied
Operation
No/Yes
NO
Tells OAU to run in unoccupied
mode
FATALOAU
OAU.F
Shut Down on Fan Failure No/Yes
YES
Tells OAU to shut off if one of its
fans fail
MODWHEEL
M.WHL
Modulating Wheel Install
No/Yes
NO
Determine if the OAU’s wheel is a
modulating one
MINOACFM
OA.MN
Minimum Outside Air
CFM
0 to 32000
CFM
375: 04
800: 0506
1000: 07
2500: 08-12
3000: 14
4000: 17-20
5000: 24-28
Sets Design OA CFM for ventilation
MINDCVSP
DCV.M
Min DCV Outside Air CFM 0 to 32000
CFM
100: 04
250: 05-06
600: 07
1000: 08-12
1500: 14-24
2000: 24-28
Sets absolute minimum OA CFM for
ventilation
PEX_CTL
PEX.C
Power Exhaust Control
0=offset CFM
1=BP
0
Determine how to control the
exhaust fans
EXOFFSET
PE.OF
Power Exhaust CFM
Offset
- 17000 to 17000 CFM –200
Sets offset CFM setpoint of exhaust
based on intake
OAU_BPSP
BP.SP
Building Pressure Setpnt
- 0.25 to 0.25
in H
2
O 0.05
Sets required building pressure
OATEMPER
OA.TM
Outside Air Tempering
Disable/Enable
Disable
Determine if there is tempering
heater installed
OATMPLOC
TM.LO
OA Tempring Lockout
Temp
0 to 80
°F
60
Sets the outside temp and below to
allow tempering
OATMPSPT
TM.SP
OA Tempring SAT
Setpoint
35 to 80
°F
55
Sets target supply air temperature
during tempering
OACFM_K
OAC.K
Outside Air CFM k Factor 0.8 to 1.2
1.0
Sets outside air curve correction
factor
EXCFM_K
EXC.K
Exhaust Air CFM k Factor 0.8 to 1.2
1.0
Sets exhaust air curve correction
factor
EFB_ENBL
EFBE
ERV Fan Boost Enable
No/Yes
NO
Tells RTU to adjust fan speed for
low outside air CFM
Summary of Contents for /50HC 04-28
Page 69: ...69 Fig 24 Typical Control Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Page 70: ...70 Fig 25 Typical Power Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Page 71: ...71 Fig 26 Typical Control Diagram for 50HC 04 14 Units 50HC 14 shown ...
Page 72: ...72 Fig 27 Typical Power Diagram for 50HC 04 14 Units 50HC 14 Non Humidi MiZer shown ...
Page 73: ...73 Fig 28 Typical Control Diagram 48HC 17 28 Units ...
Page 74: ...74 Fig 29 Typical Control Diagram 50HC 17 28 Units ...
Page 75: ...75 Fig 30 Typical Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Page 76: ...76 Fig 31 Typical Non Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Page 89: ...89 Fig 42 Modulating ERV Wiring Schematic ...
Page 90: ...90 Fig 43 EnergyX ERV Control Box Component Layouts ...
Page 101: ...101 Fig 59 Exhaust Fan Assembly Removal Exhaust Fan Assembly ...
Page 141: ......