38
* These can be viewed under Run Status
→
OAU or Operating Modes
→
OAU on the scrolling marquee or Navigator™ display.
† These can be viewed under the CCN tables OAUDISP or OAU_DIAG with a CCN device.
Table 13 — Status Points — ERV Writes These Points to
Comfort
Link Controller
CCN POINT*
SCROLLING
MARQUEE POINT†
EXPANDED TEXT
RANGE
UNITS
FUNCTION
OAU_RUN
OA.RN
OAU System Run State
1=AUTO
2=OFF
3=TEST
High level ERV state
OAU_MODE
OA.OP
OAU Operating Mode
0=Off
1=ERV (DCV)
2=Free Cooling
3=OA Tempering
4=Defrost
5=Test
6=Ext. Mode 1
7=Ext. Mode 2
8=Ext. Mode 3
ERV’s current operating mode
UPC_VER
UPC
UPC Software Version
0 to 9999
Active UPC software version
OAU_VER
OAU
OA Unit Software Version
0 to 9999
Active EXCB software version
ACTOACFM
A.OA
Actual Outside Air CFM
0 to 32000
CFM
Real Time CFM being brought in
ACTEXCFM
A.EX
Actual Exhaust Air CFM
0 to 32000
CFM
Real Time CFM being exhausted
CMDOACFM
C.OA
Command Outside Air CFM
0 to 32000
CFM
Commanded CFM to bring in
CMDEXCFM
C.EX
Command Exhaust Air CFM
0 to 32000
CFM
Commanded CFM to exhaust
OAU_LAT
LAT
OAU Leaving Air Temp
xxx.x
°F
Air temperature leaving the ERV (RTU intake)
OAU_EXAT
EXAT
OAU Exhaust Air Temp
xxx.x
°F
Air Temperature leaving the ERV (exhaust)
OAU_BP
BP
Building Pressure
–0.25 to 0.25
in H
2
O Current building pressure
OAUDMPR
2P.DM
OAU 2 --- position Damper
Close/Open
Exhaust damper position status
OAUWHEEL
WHL
OAU Wheel Speed
0 to100
%
Current ERV wheel speed
OAFANSPD
OA.FS
OAU OA Fan Speed
0 to100
%
Current ERV’s intake fan(s) speed
OAUPESPD
EX.FS
OAU Exhaust Fan Speed
0 to100
%
Current ERV’s exhaust fan(s) speed
OAHEATER
OA.HT
OAU Tempering Heater
0 to 100
%
ERV’s SCR heater commanded capacity
OAUALRM1
ALM.1
OAU Motor Failure Alarm
Off/On
ERV’s motor failure alarm status
OAUALRM2
ALM.2
OAU Dirty Filter Alarm
Off/On
ERV’s dirty filter alarm status
OAUALRM3
ALM.3
OA Low CFM Alarm
Off/On
ERV’s low CFM alarm status
OAUALRM4
ALM.4
OAU Alarm
Off/On
ERV’s General Alarm status
Summary of Contents for /50HC 04-28
Page 69: ...69 Fig 24 Typical Control Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Page 70: ...70 Fig 25 Typical Power Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Page 71: ...71 Fig 26 Typical Control Diagram for 50HC 04 14 Units 50HC 14 shown ...
Page 72: ...72 Fig 27 Typical Power Diagram for 50HC 04 14 Units 50HC 14 Non Humidi MiZer shown ...
Page 73: ...73 Fig 28 Typical Control Diagram 48HC 17 28 Units ...
Page 74: ...74 Fig 29 Typical Control Diagram 50HC 17 28 Units ...
Page 75: ...75 Fig 30 Typical Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Page 76: ...76 Fig 31 Typical Non Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Page 89: ...89 Fig 42 Modulating ERV Wiring Schematic ...
Page 90: ...90 Fig 43 EnergyX ERV Control Box Component Layouts ...
Page 101: ...101 Fig 59 Exhaust Fan Assembly Removal Exhaust Fan Assembly ...
Page 141: ......