103
SSP.B
Suction Pressure B
xxx.x
psig
SSP_B
SCT.B
Sat. Condenser Temp B
xxx.x
°F
SCT_B
SCP.B
Condenser Pressure B
xxx.x
psig
SCP_B
HEAT
Heating Status
HEATDISP
DMD.H
Heating Demand
xxx.x
^F
HEAT_DMD
AVL.H
Available Heating Stages
x
AVLHSTGS
REQ.H
Requested Heating Stages
x
REQHSTGS
MAX.H
Max Allowed Heat Stages
x
MAXHSTGS
forcible
LMT.H
Max Heat Stage In Effect
x
HSTGLIMT
F.SPD
Commanded Fan Speed
xxx
%
FANSPEED
HT.1
Heat Stage 1 Relay
Off/On
HEAT_1
TG.H1
Heat Stage 1 Timeguard
xxx
sec
TIMGD_H1
HT.2
Heat Stage 2 Relay
Off/On
HEAT_2
TG.H2
Heat Stage 2 Timeguard
xxx
sec
TIMGD_H2
ECON
Economizer Status
ECONDISP
EC.CP
Econo Commanded Position xxx
%
ECONOCMD
EC.AP
Econo Actual Position
xxx
%
ECONOPOS
EC.MP
Min Position in Effect
xxx %
MIN_POS forcible
IAQ.S
IAQ Level (switch)
Low/High
IAQIN
IAQ
IAQ Level (sensor)
xxxx
IAQ
OAT
Outdoor Air Temperature
xxx.x
°F
OA_TEMP
RAT
Return Air Temperature
xxx.x
°F
RETURN_T
ENTH
Outdoor Enthalpy Switch
Low/High
ENTHALPY
OAQ
OAQ Level (sensor)
xxxx
OAQ
PE.1
Power Exhaust 1 Relay
Off/On
PE_1
PE.2
Power Exhaust 2 Relay
Off/On
PE_2
EC.CP
Econo Command Position
ECONOCMD
EC.AP
Econo Actual Position
ECONOPOS
EC.CL
OK To Use Econo for T24
T24ECOOL
OK.TS
OK Test Mech. D/C Act.
OKTSTMDA
RO.OK
RAT-OAT OK for Title 24
T24RO_OK
PR.SA
Title 24 Previous SAT
T24PRSAT
PR.SA
Title 24 Econ Samp Pos
T24ECSMP
SA.CT
Title 24 SAT Check Time
T24SATCT
TS.MK
Title 24 Test Mark
T24tSMRK
ELP.S
Elapsed Seconds
ELAPSECS
S.VFD
SUPPLY FAN VFD
VFD_DATA
VFD1
Status Word 1
NNNNN
VFD1STAT
SPD
VFD1 Actual Speed %
NNN.n
%
VFD1_SPD
RPM
VFD1 Actual Motor RPM
NNNNN
VFD1RPM
FREQ
VFD1 Actual Motor Freq
NNN.n
VFD1FREQ
AMPS
VFD1 Actual Motor Amps
NNN.n
amps
VFD1AMPS
TORQ
VFD1 Actual Motor Torque
NNNN.n
%
VFD1TORQ
PWR
VFD1 Actual Motor Power
NNNN.nn
kW
VFD1PWR
VDC
VFD1 DC Bus Voltage
NNNN
volts
VFD1VDC
V.OUT
VFD1 Output Voltage
NNNN
volts
VFD1VOUT
TEMP
VFD1 Transistor Temp (C)
NNN
VFD1TEMP
RUN.T
VFD1 Cumulative Run Time NNNNN
hours
VFD1RUNT
KWH
VFD1 Cumulative kWh
NNNNN
VFD1KWH
LFC
VFD1 Last Fault Code
NNNNN
VFD1LFC
(CCN Points Only)
VFD1 DI1 State
Open/Close
VFD1_DI1
VFD1
DI2 State
Open/Close
VFD1_DI2
DI3 State
Open/Close
VFD1_DI3
DI4 State
Open/Close
VFD1_DI4
DI5 State
Open/Close
VFD1_DI5
DI6 State
Open/Close
VFD1_DI6
AI1 (% of range)
NNN.n
%
VFD1_AI1
AI2 (% of range)
NNN.n
%
VFD1_AI2
APPENDIX A — LOCAL DISPLAY AND CCN TABLES (cont)
Table A — Mode — Run Status (cont)
ITEM EXPANSION
RANGE
UNITS
CCN TABLE/
SUB-TABLE
CCN POINT
CCN
WRITE
STATUS
Summary of Contents for /50HC 04-28
Page 69: ...69 Fig 24 Typical Control Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Page 70: ...70 Fig 25 Typical Power Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Page 71: ...71 Fig 26 Typical Control Diagram for 50HC 04 14 Units 50HC 14 shown ...
Page 72: ...72 Fig 27 Typical Power Diagram for 50HC 04 14 Units 50HC 14 Non Humidi MiZer shown ...
Page 73: ...73 Fig 28 Typical Control Diagram 48HC 17 28 Units ...
Page 74: ...74 Fig 29 Typical Control Diagram 50HC 17 28 Units ...
Page 75: ...75 Fig 30 Typical Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Page 76: ...76 Fig 31 Typical Non Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Page 89: ...89 Fig 42 Modulating ERV Wiring Schematic ...
Page 90: ...90 Fig 43 EnergyX ERV Control Box Component Layouts ...
Page 101: ...101 Fig 59 Exhaust Fan Assembly Removal Exhaust Fan Assembly ...
Page 141: ......