APPENDIX A — LOCAL DISPLAY AND CCN TABLES (cont)
Table I — Mode — Time Clock (cont)
ITEM
EXPANSION
RANGE
UNITS
DEFAULT
CCN TABLE/Sub-TABLE
CCN POINT
HOL.L
Holiday Schedule
HOLIDAY
HOL.x
Holiday x
HOLDYxxS
MON.x
Holiday Start Month
1 to 12 = January
to December
0 HOLMONxx
DAY.x
Holiday Start Day
1 to 31
0
HOLDAYxx
LEN.x
Holiday Duration (days)
1 to 99
0
HOLLENxx
(repeat up to
x=9 Holidays)
(repeat up to
xx=30
Holidays
Table J — CCN Only Tables
ITEM
EXPANSION
RANGE
UNITS
DEFAULT
CCN TABLE/Sub-TABLE
CCN POINT
(ALARMDEF =
CCN only)
ALARMDEF
Alarm Routing Control
00000000 to
11111111
11000000 ALRM_CNT
Equipment Priority
0 to 7
5
EQP_TYPE
Comm Failure Retry Time
1 to 240
min
10
RETRY_TM
Re-Alarm Time
1 to 255
min
180
RE-ALARM
Alarm System Name
up to 8 alphanum
48_50_HC
ALRM_NAM
(CTLRID = CCN
only)
CTLR-ID
Device Name:
48_50_HC
Description: text
string
Location: text
string
Software Part Number:
CESR131504-XX-
XX
Model Number:
Serial Number:
Reference Number:
Table K — Mode — Operating Modes
ITEM
EXPANSION
RANGE
UNITS
CCN TABLE/Sub-
TABLE
CCN POINT
CCN WRITE
STATUS
DISPLAY
WRITE
STATUS
OPERATING
MODES
MAINTENANCE
DISPLAY
MODE
Control Modes
MODES
SYS
Unit operation disabled
Unit operation enabled
Service test enabled
SYS_MODE_TEXT1
SYS_MODE_TEXT2
(table only)
SYS_MODE_TEXT3
table only)
HVAC
HVAC Operation Disabled
Ventilation (fan-only)
Cooling
Free Cooling
Unoccupied Free Cooling
Reheat1
Reheat2
Reheat1 / Reheat2
Heating
HVACMODE_TEXT_1
HVACMODE_TEXT_2
(table only)
HVACMODE_TEXT_3
(table only)
F.MOD
Indoor Fan Mode
x
IDF_MODE
F.OVR
Fan Override in Effect
No/Yes
FAN_OVR
HV.DN
Remote HVAC Mode Disable No/Yes
HVACDOWN
forcible
EFF.C
Cool Setpoint In Effect
xx.x
°F
CSP_EFF
EFF.H
Heat Setpoint In Effect
xx.x
°F
HSP_EFF
OCC
Currently Occupied
No/Yes
OCCUPIED
forcible
forcible
T.OVR
Timed Override in Effect
No/Yes
MODETOVR
LINK
Linkage Active
No/Yes
MODELINK
D.LMT
Demand Limit In Effect
No/Yes
MODEDMDL
C.LOC
Compressor OAT Lockout No/Yes
COMPLOCK
H.LOC
Heat OAT Lockout
No/Yes
HEATLOCK
OK.EC
OK to Use Economizer?
No/Yes
ECONCOOL
Summary of Contents for /50HC 04-28
Page 69: ...69 Fig 24 Typical Control Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Page 70: ...70 Fig 25 Typical Power Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Page 71: ...71 Fig 26 Typical Control Diagram for 50HC 04 14 Units 50HC 14 shown ...
Page 72: ...72 Fig 27 Typical Power Diagram for 50HC 04 14 Units 50HC 14 Non Humidi MiZer shown ...
Page 73: ...73 Fig 28 Typical Control Diagram 48HC 17 28 Units ...
Page 74: ...74 Fig 29 Typical Control Diagram 50HC 17 28 Units ...
Page 75: ...75 Fig 30 Typical Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Page 76: ...76 Fig 31 Typical Non Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Page 89: ...89 Fig 42 Modulating ERV Wiring Schematic ...
Page 90: ...90 Fig 43 EnergyX ERV Control Box Component Layouts ...
Page 101: ...101 Fig 59 Exhaust Fan Assembly Removal Exhaust Fan Assembly ...
Page 141: ......