113
A.OAU
Outside Air unit Alarms
No/Yes
Yes
OAU_AL
PID
PID Configurations
PID_CFG 33
EC.P
Economizer PID - kP
0.00 to 99.90
2.5
ECONO_P
EC.I
Economizer PID - kI
0.00 to 99.90
0.12
ECONO_I
EC.D
Economizer PID - kD
0.00 to 99.90
1
ECONO_D
EC.DT
Economizer PID - rate
10.00 to 180.00 secs
15
ECONO_DT
EC.DB
Economizer PID Deadband
0 to 25
%
3
ECONBAND
LK.P
Linkage Staging PID - kP
0.00 to 99.90
10
LINK_P
LK.I
Linkage Staging PID - kI
0.00 to 99.90
5
LINK_I
LK.D
Linkage Staging PID - kD
0.00 to 99.90
5
LINK_D
LK.DT
Linkage Staging PID - rate
10.00 to 180.00 secs
30
LINK_DT
(GENERIC = CCN
only)
GENERICS
POINT 01 Definition
Point_01
POINT 02 Definition
Point_02
POINT 03 Definition
Point_03
POINT 04 Definition
Point_04
POINT 05 Definition
Point_05
POINT 06 Definition
Point_06
POINT 07 Definition
Point_07
POINT 08 Definition
Point_08
POINT 09 Definition
Point_09
POINT 10 Definition
Point_10
POINT 11 Definition
Point_11
POINT 12 Definition
Point_12
POINT 13 Definition
Point_13
POINT 14 Definition
Point_14
POINT 15 Definition
Point_15
POINT 16 Definition
Point_16
POINT 17 Definition
Point_17
POINT 18 Definition
Point_18
POINT 19 Definition
Point_19
POINT 20 Definition
Point_20
TRIM
Sensor Calibration
(CCN TRIM - see
Maintenance
Display)
SPT.C
Space Temp Calibration
-30 to 130
°F
49
SPT.T
Space Temp Trim
-30 to 30
^F
0
49
SAT.C
Supply Air Temp Calib.
-30 to 130
°F
49
SAT.T
Supply Air Temp Trim
-30 to 30
^F
0
49
RAT.C
Return Air Temp Calib.
-30 to 130
°F
49
RAT.T
Return Air Temp Trim
-30 to 30
^F
0
49
CCN
CCN Configuration
CCN
CONFIGURATION
48-50 HC
CCN.A
CCN Element Number
1 to 239
1
CCNADD
32
CCN.B
CCN Bus Number
0 to 239
0
CCNBUS
32
BAUD
CCN Baud Rate
1=2400
2=4800
3=9600
4=19200
5=38400
CCNBAUDD 32
BROD
CCN Broadcast Config.
BRODEFS
B.TIM
CCN Time/Date Broadcast
No/Yes
No
CCNBC
32
B.OAT
CCN OAT Broadcast
No/Yes
No
OATBC
32
B.GS
Global Schedule Broadcst
No/Yes
No
GSBC
32
B.ACK
CCN Broadcast Ack’er
No/Yes
No
CCNBCACK
32
SCH.O
CCN Schedule Overrides
SCHEDOVR
SCH.N
Schedule Number
0 = Always
Occupied
1-64 = Local
Schedule
65-99 = Global
Schedule
0 SCHEDNUM
32
HOL.G
Accept Global Holidays
No/Yes
No
HOLIDAYT
32
APPENDIX A — LOCAL DISPLAY AND CCN TABLES (cont)
Table H — Mode — Configuration (cont)
ITEM EXPANSION
RANGE
UNITS
DEFAULT
CCN TABLE/
SUB-TABLE
CCN POINT PAGE
NO.
Summary of Contents for /50HC 04-28
Page 69: ...69 Fig 24 Typical Control Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Page 70: ...70 Fig 25 Typical Power Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Page 71: ...71 Fig 26 Typical Control Diagram for 50HC 04 14 Units 50HC 14 shown ...
Page 72: ...72 Fig 27 Typical Power Diagram for 50HC 04 14 Units 50HC 14 Non Humidi MiZer shown ...
Page 73: ...73 Fig 28 Typical Control Diagram 48HC 17 28 Units ...
Page 74: ...74 Fig 29 Typical Control Diagram 50HC 17 28 Units ...
Page 75: ...75 Fig 30 Typical Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...