135
SCH.O
CCN Schedule Overrides
SCHEDOVR
SCH.N
Schedule Number
0 = Always
Occupied
1-64 = Local
Schedule
65-99 = Global
Schedule
0 SCHEDNUM
HOL.G
Accept Global Holidays
No/Yes
No
HOLIDAYT
OV.TL
Override Time Limit
0 to 4
hours
4
OTL
OV.EX
Timed Override Hours
0 to 4
hours
-
OVR_EXT
OV.SP
SPT Override Enabled
No/Yes
Yes
TIMEOVER
LDSH
CCN LOADSHED CONFIG.
LOADSHED
S.GRP
Loadshed Group Number
0 to 16
0
SHED_NUM
R.MXC
Redline Max Cool Stages
0 to 3
2
MAXCREDL
S.MXC
Loadshed Max Cool Stages
0 to 3
2
MAXCSHED
R.MXH
Redline Max Heat Stages
0 to 2
2
MAXHREDL
S.MXH
Loadshed Max Heat Stages
0 to 2
2
MAXHSHED
APPENDIX C — VARIABLE FREQUENCY DRIVE (VFD) (cont)
Table X — Mode — Configuration (cont)
ITEM EXPANSION
RANGE
UNITS
DEFAULT
CCN TABLE/
Sub- TABLE
CCN POINT
ENTRY
Summary of Contents for /50HC 04-28
Page 69: ...69 Fig 24 Typical Control Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Page 70: ...70 Fig 25 Typical Power Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Page 71: ...71 Fig 26 Typical Control Diagram for 50HC 04 14 Units 50HC 14 shown ...
Page 72: ...72 Fig 27 Typical Power Diagram for 50HC 04 14 Units 50HC 14 Non Humidi MiZer shown ...
Page 73: ...73 Fig 28 Typical Control Diagram 48HC 17 28 Units ...
Page 74: ...74 Fig 29 Typical Control Diagram 50HC 17 28 Units ...
Page 75: ...75 Fig 30 Typical Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Page 76: ...76 Fig 31 Typical Non Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Page 89: ...89 Fig 42 Modulating ERV Wiring Schematic ...
Page 90: ...90 Fig 43 EnergyX ERV Control Box Component Layouts ...
Page 101: ...101 Fig 59 Exhaust Fan Assembly Removal Exhaust Fan Assembly ...
Page 141: ......