116
APPENDIX A — LOCAL DISPLAY AND CCN TABLES (cont)
Table K — Mode — Operating Modes (cont)
ITEM
EXPANSION
RANGE
UNITS
CCN TABLE/Sub-
TABLE
CCN POINT
CCN WRITE
STATUS
DISPLAY
WRITE
STATUS
COOL
Cool Mode Diagnostic
COOLDIAG
COOL
In Cooling Mode?
No/Yes
IN_COOL
OK.CL
OK to Select Cool Mode?
No/Yes
OKTOCOOL
MS.TG
Mode Select Timeguard
xxx
secs
COOLMSTG
OK.EC
OK to Use Economizer?
No/Yes
ECONCOOL
OK.MC
OK to Use Compressors?
No/Yes
MECHCOOL
C.LOC
Compressor OAT Lockout No/Yes
COMPLOCK
CA.LO
Circuit A Lockout Temp
xxx
°F
OATLCMPA
CB.LO
Circuit B Lockout Temp
xxx
°F
OATLCMPB
F.MOD
Indoor Fan Mode
x
IDF_MODE
F.SPD
Commanded Fan Speed
NNN
%
FANSPEED
AVL.C
Available Cooling Stages
x
AVLCSTGS
REQ.C
Requested Cooling Stages
x
REQCSTGS
LMT.C
Max Cool Stage In Effect
x
CSTGLIMT
ACT.C
Actual Cooling Stages
x
ACTCSTGS
CMP.A
Circuit A Compressor(s)
Off/On
COMP_A
CMP.B
Circuit B Compressor
Off/On
COMP_B
ST.A
Circuit A Strikes
x
ASTRIKES
ST.B
Circuit B Strikes
x
BSTRIKES
HPS.A
Ckt A Hi Pres Sw Check
No/Yes
INHPSCKA
HPS.B
Ckt B Hi Pres Sw Check
No/Yes
INHPSCKB
SAT
Supply Air Temperature
SAT
Supply Air Temperature
xxx.x
°F
SAT_DISP
SA.DM
Supply Air Temp Demand
xxx.x
^F
SAT_DMD
SA.PD
SAT Cool Demand (+) Level xx.x
^F
SAT_POS
SA.ND
SAT Cool Demand (- ) Level xx.x
^F
SAT_NEG
SAT.U
Minimum SAT Upper Level
xx.x
°F
SATMIN_H
SAT.L
Minimum SAT Lower Level
xx.x
°F
SATMIN_L
SA.TR
Supply Air d/dt (F/min) xxxx.x
SATTREND
SA.DR
SAT Delta Reference Temp
xxx.x
°F
SAT_REF
SPT
Space Temperature
SPT
Space Temperature
xxx.x
°F
SPACE_T
forcible
forcible
DMD.C
Cooling Demand
xxx.x
^F
COOL_DMD
TRD.C
Cool Demand d/dt (F/min)
xxx.x
CLDTREND
CL.PD
SPT Cool Demand (+) Level xx.x
^F
DEM_POS
CL.ND
SPT Cool Demand (- ) Level xx.x
^F
DEM_NEG
C.LAG
Cool Thermal Lag Factor
x.x
COOL_LAG
COOL_LAG
HMZR
Humidimizer
REHT
Humidimizer Equipped
No/Yes
REHEAT
HUM
Space Humidity Switch
Low/High
HUM_STAT
forcible
SP.RH
Space Humidity Sensor xxx.x
%
SPRH
forcible forcible
R.LO.A
Reheat2 OAT Lockout A
No/Yes
RHALOCK
RA.LO
Reheat2 OAT Limit A
xx
°F
OATLRH_A
R.LP.A
Reheat2 SSP Override A
No/Yes
RHALPOV
R.LO.B
Reheat2 OAT Lockout B
No/Yes
RHBLOCK
RB.LO
Reheat2 OAT Limit B
xx
°F
OATLRH_B
R.LP.B
Reheat2 SSP Override B
No/Yes
RHBLPOV
AVL.R
Available Reheat2 Stages
x
AVLRSTGS
REQ.R
Requested Reheat2 Stages
x
REQRSTGS
ACT.R
Actual Reheat2 Stages
x
ACTRSTGS
CRC
Cool->Reheat1 Control
Off/On
CRC
RH2.A
Reheat2 Valve A
Off/On
RH2_A
RH2.B
Reheat2 Valve B
Off/On
RH2_B
HEAT
Heat Mode Diagnostic
HEATDIAG
HEAT
In Heating Mode?
No/Yes
IN_HEAT
Summary of Contents for /50HC 04-28
Page 69: ...69 Fig 24 Typical Control Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Page 70: ...70 Fig 25 Typical Power Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Page 71: ...71 Fig 26 Typical Control Diagram for 50HC 04 14 Units 50HC 14 shown ...
Page 72: ...72 Fig 27 Typical Power Diagram for 50HC 04 14 Units 50HC 14 Non Humidi MiZer shown ...
Page 73: ...73 Fig 28 Typical Control Diagram 48HC 17 28 Units ...
Page 74: ...74 Fig 29 Typical Control Diagram 50HC 17 28 Units ...
Page 75: ...75 Fig 30 Typical Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Page 76: ...76 Fig 31 Typical Non Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Page 89: ...89 Fig 42 Modulating ERV Wiring Schematic ...
Page 90: ...90 Fig 43 EnergyX ERV Control Box Component Layouts ...
Page 101: ...101 Fig 59 Exhaust Fan Assembly Removal Exhaust Fan Assembly ...
Page 141: ......