205
APPENDIX B — CCN TABLES (cont)
Configuration Tables (cont)
RESTCON (Temperature Reset and Demand Limit)
DESCRIPTION
VALUE
UNITS
POINT NAME
NETWORK
ACCESS
COOLING RESET
Cooling Reset Type
N
Range:
0 = No Reset
1 = 4-20 mA Input
2 = Out Air Temp
3 = Not Supported
4 = Space Temp
Default: 0
CRST_TYP
Configuration
4-20 MA RESET
4-20 - Degrees Reset
NNN.n
Range: –30 to 30 (–16.7 to 16.7)
Default: 10 (5.6)
'
F (
'
C)
420_DEG
Configuration
REMOTE RESET
Remote - No Reset Temp
NNN.N
Range: 0.0 to 125.0 (–17.8 to 51.7)
Default: 10.0 ( 12.2)
°F (°C)
REM_NO
Configuration
Remote - Full Reset Temp
NNN.N
Range: 0.0 to 125.0 (–17.8 to 51.7)
Default: 10.0 ( 12.2)
°F (°C)
REM_FULL
Configuration
Remote - Degrees Reset
NNN.n
Range: –30 to 30 (–16.7 to 16.7)
Default: 10 (5.6)
'
F (
'
C)
REM_DEG
Configuration
RETURN TEMPERATURE RESET
Return - No Reset Temp
Feature Not Supported
NNN.n
Range: 0.0 to 30.0 (0.0 to 16.7)
Default: 10.0 (5.6)
'
F (
'
C)
RTN_NO
Configuration
Return - Full Reset Temp
Feature Not Supported
NNN.n
Range: 0.0 to 10.0 (0.0 to 16.7)
Default: 0.0 (0.0)
'
F (
'
C)
RTN_FULL
Configuration
Return - Degrees Reset
Feature Not Supported
NNN.n
Range: –30 to 30 (–16.7 to 16.7)
Default: 0.0 (0.0)
'
F (
'
C)
RTN_DEG
Configuration
DEMAND LIMIT
Demand Limit Select
N
Range:
0 = None
1 = Switch
2 = 4-20 Input
3 = CCN Loadshed
Default: 0
DMD_CTRL
Demand Limit at 20 mA
NNN
Range: 0 to 100
Default: 100
%
DMT20MA
Loadshed Group Number
NN
Range: 0 to 99
Default: 0
SHED_NUM
Loadshed Demand Delta
NN
Range: 0 to 60
Default: 0
%
SHED_DEL
Maximum Loadshed Time
NNN
Range: 0 to 120
Default: 60
min
SHED_TIM
Demand Limit Switch 1
NNN
Range: 0 to 100
Default: 80
%
DLSWSP1
Demand Limit Switch 2
NNN
Range: 0 to 100
Default: 50
%
DLSWSP2