APPENDIX C — BACNET COMMUNICATION OPTION (cont)
Table G — Network Points List (cont)
LEGEND
POINT DESCRIPTION
POINT NAME
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT ID
BACNET
OBJECT NAME
Machine Control Type
MSV Point for i-Vu /
BACnet based on
CCN point
CTRLTYPE
R
4
1 = VAV
2 = Invalid
3 = Tstat Multi
4 = Tstat 2 Stg
5 = SPT Multi
6 = Invalid
7 = PCT Cap
8 = Dual Tsat
9 = VAV Setpoint
MSV:3
ctrltype_msv_1
Machine Operating Hours
HR_MACH
R
hr
0-9999
AV:57
mr_mach_1
Machine Starts
CY_MACH
R
0-9999
AV:58
cy_mach_1
Minimum Comp. On Time
MODE_23
R
ON_OFF
BV:49
mode_23_1
Minimum Load Valve Relay
MLV_RLY
R
ON_OFF
BV:79
mlv_rly_1
Minimum OFF time active
MODE_10
R
ON_OFF
BV:38
mode_10_1
Minutes Left for Start
MIN_LEFT
R
min
00:00-15:00
AV:32
min_left_1
Minutes Off Time
DELAY
R/W
min
0
0-15
AV:42
delay_1
Occupied
OCC
R
YES_NO
BV:2008
occ_status_1
Outside Air Temperature
OAT
R/W
°F
-40-245
AV:1003
oa_temp
Override Modes in Effect
MODE
R
YES_NO
BV:5
mode_1
Percent Available Cap.
CAPA_A
R
%
0-100
AV:12
capa_a_1
Percent Available Cap.
CAPB_A
R
%
0-100
AV:22
capb_a_1
Percent Total Capacity
CAP_T
R
%
0-100
AV:3
cap_t_1
Percent Total Capacity
CAPA_T
R
%
0-100
AV:11
capa_t_1
Percent Total Capacity
CAPB_T
R
%
0-100
AV:21
capb_t_1
Ramp Load Limited
MODE_5
R
ON_OFF
BV:33
mode_5_1
Requested Stage
STAGE
R
0-99
AV:9
stage_1
Return Air Temperature
RETURN_T
R
°F
0-125
AV:1010
ra_temp_1
Saturated Condensing Tmp
SCTA
R
°F
-40-245
AV:40
scta_1
Saturated Condensing Tmp
SCTB
R
°F
-40-245
AV:39
sctb_1
Saturated Suction Temp
SSTA
R
°F
-40-245
AV:17
ssta_1
Saturated Suction Temp
SSTB
R
°F
-40-245
AV:26
sstb_1
SCT Delta for Compressor A1
A1SCTDT
R/W
°F
0-99
AV:41
a1sctdt_1
SCT Delta for Compressor A2
A2SCTDT
R/W
°F
0-99
AV:46
a2sctdt_1
SCT Delta for Compressor B1
B1SCTDT
R/W
°F
0-99
AV:47
b1sctdt_1
SCT Delta for Compressor B2
B2SCTDT
R/W
°F
0-99
AV:48
b2sctdt_1
Slow Change Override
MODE_9
R
ON_OFF
BV:37
mode_9_1
Space T Cool Set Point
SPT_SP
R/W
°F
78.0
0-999
AV:51
spt_sp_1
Space T SP Plus Offset
SPSP_PO
R/W
°F
0-999
AV:76
spsp_po_1
Space Temp Control Mode
SPTMODE
R
0 = Cool Off
1 = Lo Cool
2 = Hi Cool
3 = Cool On
AV:52
sptmode_1
Space Temperature
SPT
R/W
°F
0-999
AV:2007
space_temp
Space Temperature Offset
SPTO
R/W
°F
0-99
AV:55
spto_1
Space Temperature Offset
Enable
SPTOSENS
R/W
ENA_DIS
BV:10
sptosens_1
Space Temperature Offset
Range
SPTO_RNG
R/W
°F
-20-99
AV:75
spto_rng_1
Space Temperature Sensor
SPTSENS
R
ENA_DIS
BV:11
sptsens_1
Suction Pressure
SP_A
R
psig
0-999
AV:14
sp_a_1
Suction Pressure
SP_B
R
psig
0-999
AV:24
sp_b_1
Suction Superheat
Temperature
SH_A
R
°F
-40-245
AV:44
sh_a_1
Suction Superheat
Temperature
SH_B
R
°F
-40-245
AV:45
sh_b_1
Supply Air Set Point
SAT_SP
R
°F
0-125
AV:78
sat_sp_1
Supply Air Temperature
SUPPLY_T
R
°F
-40-245
AV:1008
sa_temp_1
System Demand Limiting
R
Inactive_Active
BV:83
dem_lmt_act_1
R
—
Read
W
—