![Carrier 38APD115 Manual Download Page 195](http://html.mh-extra.com/html/carrier/38apd115/38apd115_manual_2560531195.webp)
195
APPENDIX B — CCN TABLES
Status Tables
A_UNIT (General Unit Parameters)
CIRCA_AN (Circuit A Analog Parameters)
DESCRIPTION
VALUE
UNITS
POINT NAME
NETWORK
ACCESS
Control Mode
N
0 = SERVICE
1 = OFF Local
2 = OFF CCN
3 = OFF Time
4 = Emergency
5 = ON Local
6 = ON CCN
7 = ON Time
8 = IDF OFF
9 = SPT SATIS
STAT
Read Only
Space Temp Control Mode
N
0 = Cool Off
1 = Lo Cool
2 = Hi Cool
3 = Cool On
SPTMODE
Read Only
Occupied
NO/YES
OCC
Read Only
CCN Chiller
STOP/START
CHIL_S_S
Read/Write
Alarm State
N
0 = Normal
1 = Alert
2 = Alarm
ALM
Read Only
Cap Req/Setpoint Signal
NN.n
mA
COOL_MA
Read Only
Active Demand Limit
NNN
%
DEM_LIM
Read/Write
Override Modes in Effect
NO/YES
MODE
Read Only
Percent Total Capacity
NNN
%
CAP_T
Read Only
Requested Stage
NN
STAGE
Read Only
Active Setpoint
NNN.n
°F (°C)
SP
Read Only
Control Point
NNN.n
°F (°C)
CTRL_PNT
Read/Write
Return Air Temperature
NNN.n
°F (°C)
RETURN_T
Read/Write
Supply Air Temperature
NNN.n
°F (°C)
SUPPLY_T
Read/Write
Emergency Stop
Enable/EMStop
EMSTOP
Read/Write
Minutes Left for Start
5 Character ASCII
MIN_LEFT
Read Only
DESCRIPTION
VALUE
UNITS
POINT NAME
NETWORK
ACCESS
CIRCUIT A ANALOG VALUES
Percent Total Capacity
NNN
%
CAPA_T
Read Only
Percent Available Cap.
NNN
%
CAPA_A
Read Only
Discharge Pressure
NNN.n
psig (kPa)
DP_A
Read Only
Suction Pressure
NNN.n
psig (kPa)
SP_A
Read Only
Head Setpoint ON
NNN.n
°F (°C)
HSP_ON
Read/Write
Head Setpoint OFF
NNN.n
°F (°C)
HSP_OFF
Read/Write
Saturated Condensing Tmp
NNN.n
°F (°C)
SCTA
Read Only
Saturated Suction Temp
NNN.n
°F (°C)
SSTA
Read Only
Var Head Press Out Cir A
NNN.n
%
VHPA_ACT
Read Only
Compr Return Gas Temp
NNN.n
°F (°C)
RGTA
Read Only
Discharge Gas Temp
NNN.n
°F (°C)
DIGCMPDT
Read Only
Suction Superheat Temp
NNN.n
'
F (
'
C)
SH_A
Read Only