Table 33 — C.TYP=7 (Pct Cap) Required Configuration
*Although return air and supply air thermistors are not required, they
can be configured. If they are not installed, the values for
RAT.T
and
SAT.T
must be set to
2
.
Fig. 85 — C.TYP=7 (Pct Cap) Wiring
CONFIGURATION MODE
SUBMODE
ITEM
DISPLAY
ITEM DESCRIPTION
COMMENT
OPT1
RAT.T
X
RAT Thermistor Type
Default: 0
Range: 0 to 2
Must be set for appropriate value:
0 = 5 k
:
1 = 10 k
:
2 = None*
SAT.T
X
SAT Thermistor Type
Default: 0
Range: 0 to 2
Must be set for appropriate value:
0 = 5 k
:
1 = 10 k
:
2 = None*
OPT2
C.TYP
X
Machine Control Type
Default: 4
Range: 1 to 9
Set Item to 7 (Pct Cap)
REMOTE ON/OFF
4-20 mA
SIGNAL
GENERATOR
38AP LVT
TERMINAL STRIP
–
+
SAT (OPTIONAL)
FS1
25
24
19
18
16
14
13
11
10
8
2
1
ALM
R
MAT/RAT (OPTIONAL)
20
LLSV-B (38APD)
LLSV-A2 (38APS)
or LLSV-B2 (065)
LLSV-A
or LLSV-B (065)
CXB-J6
(38APD070-130 ONLY)
FIELD-SUPPLIED
TRANSFORMER
(REQUIRED)
RED
7
6
5
PNK
ORN
LLSV-A2
LLSV-B2
24 VAC
SECONDARY
REQUESTED
CAPACITY
SIGNAL
(REQUIRED)
A38-7281
LEGEND
NOTES:
1. Field wiring must be in accordance with local codes.
2. LVT-1 and 2 are for the alarm relay. The maximum load allowed for the alarm relay
is 5 VA sealed, 10 VA at 24 VAC. Field power supply is not required.
3. LVT-24, 25, and 2 are for control of field-supplied liquid line solenoid valve (LLSV)
15 VA sealed, 30 VA inrush at 24 VAC. Field power supply is not required.
4. For 38APD070-130 units, an additional LLSV, 15 VA sealed, 30 VA inrush at 24
VAC can be connected to CXB. A field-supplied control transformer is required, not
to exceed 75 VA.
5. All discrete inputs are 24 VAC.
6. Installation of fan status switch (FS1) is recommended. If not used, a jumper must
be installed.
7. Energy management module (EMM) is required.
8. The contacts for Remote On-Off, Fan Status Switch and Demand Limit must be
rated for dry circuit applications capable of handling a 24 VAC load up to 50 mA.
ALM R
—
Alarm Relay
CXB
—
Compressor Expansion Board
FS1
—
Fan Status Switch
LLSV-A
—
Liquid Line Solenoid, Circuit A, First Stage
LLSV-A2
—
Liquid Line Solenoid, Circuit A, Second Stage
(38APS040,050, 38APD070-130 only)
LLSV-B
—
Liquid Line Solenoid, Circuit B, First Stage
(38APS065, 38APD only)
LLSV-B2
—
Liquid Line Solenoid, Circuit B, Second Stage
(38APS065, 38APD070-130 only)
LVT
—
Low Voltage Terminal
MAT/RAT
—
Mixed Air Thermistor/Return Air Thermistor
SAT
—
Supply Air Thermistor
Factory Wiring
Field Wiring