218
APPENDIX C — BACNET COMMUNICATION OPTION (cont)
Table G — Network Points List (cont)
LEGEND
POINT DESCRIPTION
POINT NAME
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT ID
BACNET
OBJECT NAME
Temperature Reset
MODE_14
R
ON_OFF
BV:40
mode_14_1
Time Guard Active
MODE_TG
R
ON_OFF
BV:67
mode_tg_1
Timed Override in effect
MODE_6
R
ON_OFF
BV:34
mode_6_1
User Defined Analog 1
R/W
AV:2901
user_analog_1_1
User Defined Analog 2
R/W
AV:2902
user_analog_2_1
User Defined Analog 3
R/W
AV:2903
user_analog_3_1
User Defined Analog 4
R/W
AV:2904
user_analog_4_1
User Defined Analog 5
R/W
AV:2905
user_analog_5_1
User Defined Binary 1
R/W
ON_OFF
BV:2911
user_binary_1_1
User Defined Binary 2
R/W
ON_OFF
BV:2912
user_binary_2_1
User Defined Binary 3
R/W
ON_OFF
BV:2913
user_binary_3_1
User Defined Binary 4
R/W
ON_OFF
BV:2914
user_binary_4_1
User Defined Binary 5
R/W
ON_OFF
BV:2915
user_binary_5_1
Var Head Press Output
Circuit A
VHPA_ACT
R
%
0-100
AV:19
vhpa_act_1
Var Head Press Output
Circuit B
VHPB_ACT
R
%
0-100
AV:83
vhpb_act_1
Y1 Thermostat Input
Y1
R
ON_OFF
BV:27
y1_1
Y2 Thermostat Input
Y2
R
ON_OFF
BV:28
y2_1
Y3 Thermostat Input
Y3
R
ON_OFF
BV:29
y3_1
Y4 Thermostat Input
Y4
R
ON_OFF
BV:30
y4_1
R
—
Read
W
—
Write