![Carrier 38APD115 Manual Download Page 215](http://html.mh-extra.com/html/carrier/38apd115/38apd115_manual_2560531215.webp)
215
APPENDIX C — BACNET COMMUNICATION OPTION (cont)
Table G — Network Points List
LEGEND
POINT DESCRIPTION
CCN POINT NAME
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT ID
BACNET
OBJECT NAME
4-20 Cooling Demand
COOL_MA
R
mA
0-20
AV:6
cool_ma_1
4-20 mA Demand Signal
LMT_MA
R
mA
0-20
AV:36
lmt_ma_1
4-20 mA Reset Signal
RST_MA
R
mA
0-20
AV:33
rst_ma_1
Active Demand Limit
DEM_LIM
R/W
%
100
0-100
AV:2
dem_lim_1
Active Setpoint
SP
R
°F
-20-70
AV:4
sp_1
Alarm State
MSV Point for i-Vu /
BACnet based on
CCN point ALM
R
0 = Normal
1 = Alert
2 = Alarm
MSV:1
alm_msv_1
CCN Chiller
CHIL_S_S
R/W
Start
0 = Stop
1 = Start
BV:4
chil_s_s_1
CCN Loadshed Signal
DL_STAT
R
0-2
AV:37
dl_stat_1
Circuit A Run Hours
HR_CIRA
R
hr
0-9999
AV:59
hr_cira_1
Circuit A Starts
CY_CIRA
R
0-9999
AV:67
cy_cira_1
Circuit B Run Hours
HR_CIRB
R
hr
0-9999
AV:63
hr_cirb_1
Circuit B Starts
CY_CIRB
R
0-9999
AV:71
cy_cirb_1
Coil Cleaning Maint.Done
CL_MAINT
R/W
No
0 = No
1 = Yes
BV:54
cl_maint_1
Coil Cleaning Srvc Inter
SI_COIL
R/W
hr
8760
0-9999
AV:50
si_coil_1
Coil Service Countdown
CL_CDOWN
R
hr
0-9999
AV:49
cl_cdown_1
Comp A1 Load Percent
DIGITALP
R
%
0-100
AV:34
digitalp_1
Compr Return Gas Temp
RGTA
R
°F
0-125
AV:20
rgta_1
Compr Return Gas Temp
RGTB
R
°F
0-125
AV:28
rgtb_1
Compressor A1 Feedback
K_A1_FBK
R
ON_OFF
BV:16
k_a1_fbk_1
Compressor A1 Relay
K_A1_RLY
R
ON_OFF
BV:13
k_a1_rly_1
Compressor A1 Run Hours
HR_A1
R
hr
0-9999
AV:60
hr_a1_1
Compressor A1 Starts
CY_A1
R
0-9999
AV:68
cy_a1_1
Compressor A2 Feedback
K_A2_FBK
R
ON_OFF
BV:17
k_a2_fbk_1
Compressor A2 Relay
K_A2_RLY
R
ON_OFF
BV:14
k_a2_rly_1
Compressor A2 Run Hours
HR_A2
R
hr
0-9999
AV:61
hr_a2_1
Compressor A2 Starts
CY_A2
R
0-9999
AV:69
cy_a2_1
Compressor A3 Feedback
K_A3_FBK
R
ON_OFF
BV:18
k_a3_fbk_1
Compressor A3 Relay
K_A3_RLY
R
ON_OFF
BV:15
k_a3_rly_1
Compressor A3 Run Hours
HR_A3
R
hr
0-9999
AV:62
hr_a3_1
Compressor A3 Starts
CY_A3
R
0-9999
AV:70
cy_a3_1
Compressor B1 Feedback
K_B1_FBK
R
ON_OFF
BV:22
k_b1_fbk_1
Compressor B1 Relay
K_B1_RLY
R
ON_OFF
BV:19
k_b1_rly_1
Compressor B1 Run Hours
HR_B1
R
hr
0-9999
AV:64
hr_b1_1
Compressor B1 Starts
CY_B1
R
0-9999
AV:72
cy_b1_1
Compressor B2 Feedback
K_B2_FBK
R
ON_OFF
BV:23
k_b2_fbk_1
Compressor B2 Relay
K_B2_RLY
R
ON_OFF
BV:20
k_b2_rly_1
Compressor B2 Run Hours
HR_B2
R
hr
0-9999
AV:65
hr_b2_1
Compressor B2 Starts
CY_B2
R
0-9999
AV:73
cy_b2_1
Compressor B3 Feedback
K_B3_FBK
R
ON_OFF
BV:24
k_b3_fbk_1
Compressor B3 Relay
K_B3_RLY
R
ON_OFF
BV:21
k_b3_rly_1
Compressor B3 Run Hours
HR_B3
R
hr
0-9999
AV:66
hr_b3_1
Compressor B3 Starts
CY_B3
R
0-9999
AV:74
cy_b3_1
Control Method
MSV Point for i-Vu /
BACnet based on
CCN point
CONTROL
R
0
0 = Switch
1 = Occupancy
2 = CCN
MSV:5
control_msv_1
Control Mode
STAT
R
0 = Test
1 = Local Off
2 = CCN Off
3 = Clock Off
4 = Emergency
Stop
5 = Local On
6 = CCN On
7 = Clock On
8 = IDF Off
9 = SPT SATS
AV:8
stat
Control Point
CTRL_PNT
R/W
°F
-20-70
AV:5
ctrl_pnt_1
R
—
Read
W
—
Write