180
APPENDIX A — DISPLAY TABLES (cont)
Setpoints Mode and Sub-Mode Directory
NOTE: These values are values read or calculated by the controller
and cannot be changed from this item.
SUB-MODE
ITEM
DISPLAY
ITEM DESCRIPTION
COMMENT
COOL
COOLING SET POINTS
CSP.1
XX.X °F (°C)
Cooling Set Point 1
Range: 40 to 80 F (4.4 to 26.7 C)
Default: 60 F (15.6 C)
CSP.2
XX.X °F (°C)
Cooling Set Point 2
Range: 40 to 80 F (4.4 to 26.7 C)
Default: 55 F (12.8 C)
SPS.P
XXX.X °F (°C)
Space T Cool Set Point
Range: 65 to 80 F (18.3 to 26.7 C)
Default: 78 F (25.6 C)
Recommended Setting: 78 F (25.6 C)
SPT.O
XX.X
ǻ
F (
ǻ
C)
Space Temperature Offset
See Note
ST.P.O
XXX.X °F (°C)
Space T SP Plus Offset
See Note
P.CAP
XXX.X %
Percent Cap. Requested
See Note
L.C.ON
X.X
ǻ
F
(
ǻ
C)
Lo Cool On Set Point
Range: –1.0 to 2.0
ǻ
F
(–0.6 to 1.1
ǻ
C)
Default: 1.0
ǻ
F (0.6
ǻ
C)
H.C.ON
XX.X
ǻ
F (
ǻ
C)
Hi Cool On Set Point
Range: 0.5 to 20.0
ǻ
F
(0.3 to 11.1
ǻ
C)
Default: 3.0
ǻ
F (1.7
ǻ
C)
Recommended Setting: 3.0
ǻ
F (1.7
ǻ
C)
L.C.OF
X.X
ǻ
F (
ǻ
C)
Lo Cool Off Set Point
Range: 0.5 to 2.0
ǻ
F
(0.3 to 1.1
ǻ
C)
Default: 0.5
ǻ
F (0.3
ǻ
C)
Recommended Setting: 0.5
ǻ
F (0.3
ǻ
C)
OAT.L
XX.X °F (°C)
OAT Lockout Temperature
Range: –20.0 to 80.0 F (-28.9 to 26.7 C)
Default: 30.0 F (–1.1 C)
HEAD
HEAD PRESSURE SET POINTS
H.SP
XXX.X °F (°C)
Head Set Point On
Range: 85 to 120 F (29.4 to 48.9 C)
Default: 115 F (46.1 C)
H.SP.F
XX.X °F (°C)
Head Set Point Off
Range: 45 to 90 F (7.2 to 32.2 C)
Default: 72.0 F (22.2 C)
F.ON
XXX.X °F (°C)
Fan On Set Point
See Note
F.OFF
XXX.X °F (°C)
Fan Off Set Point
See Note
F.DLT
XX.X
ǻ
F (
ǻ
C)
Fan Stage Delta
Range: 0.0 to 50.0
ǻ
F
(0.0 to 27.8
ǻ
C)
Default: 15.0
ǻ
F (8.3
ǻ
C)
F.TME
XXX sec
Fan Delta Active Time
Range: 0 to 300 seconds
Default: 60 seconds