APPENDIX A — DISPLAY TABLES (cont)
Configuration Mode and Sub-Mode Directory
*The Navigator™ display always uses capital letters, regardless of
the METR setting.
SUB-MODE
ITEM
DISPLAY
METR=OFF
(METR=ON)
ITEM DESCRIPTION
COMMENT
METR=OFF
(METR=ON)
DISP
DISPLAY CONFIGURATION
TEST
ON/OFF
Test Display LEDs
Default: OFF
METR
ON/OFF
Metric Display
Default: OFF
LANG
X
Language Selection
Range: 0 to 3
0 = English
1 = Espanol
2 = Francais
3 = Portuguese
Default: 0
PAS.E
ENBL/DSBL
Password Enable
Default: ENBL
PASS
XXXX
Service Password
Range: 0 to 9999
Default: 1111
UNIT
UNIT CONFIGURATION
SIZE
XXX TONS* (tons)
Unit Size
Based on Unit Model
Range: 025 to 130 (23 to 118)
25 (23) = 38APD,APS025
27 (24) = 38APD,APS027
30 (27) = 38APD,APS030
40 (36) = 38APD,APS040
50 (45) = 38APD,APS050
60 (54) = 38APD060
65 (59) = 38APS065
70 (63) = 38APD070
80 (73) = 38APD080
90 (82) = 38APD090
100 (91) = 38APD100
115 (104) = 38APD115
130 (118) = 38APD130
NCKT
X
Number of Refrigerant Circuits
Based on Unit Model
Range 1 to 2
1=38APS
2=38APD
SZ.A1
XX TONS (tons)
Compressor A1 Size
These values are set by SIZE.
and are not field-configurable.
See Configuration
o
UNIT Data
Table on page 185.
SZ.A2
XX TONS (tons)
Compressor A2 Size
SZ.A3
XX TONS (tons)
Compressor A3 Size
SZ.B1
XX TONS (tons)
Compressor B1 Size
SZ.B2
XX TONS (tons)
Compressor B2 Size
SZ.B3
XX TONS (tons)
Compressor B3 Size
FAN.S
X
Fan Sequence Number
A1.TY
YES/NO
Compressor A1 Digital
Based on Unit Model
Default:
YES = Factory Equipped
NO = Not Equipped
MAX.T
XX SECS
Maximum A1 Unload Time
Based on Unit Model
Range:
0 to 10 = 38AP025-030
0 to 8 = 38AP040-130
CCN
CCN NETWORK CONFIGS
CCNA
XXX
CCN Address
Range: 0 to 239
Default: 1
CCNB
XXX
CCN Bus Number
Range: 0 to 239
Default: 1
BAUD
X
CCN Baud Rate
Range: 1 to 5
1 = 2400
2 = 4800
3 = 9600
4 =19,200
5 =38,400
Default: 3