REMOTE ON/OFF
REQUESTED
COOLING
SETPOINT
SIGNAL
(REQUIRED)
DEMAND
LIMIT
SIGNAL
4-20 mA
SIGNAL
GENERATOR
DEMAND LIMIT STEP 2
DEMAND LIMIT STEP 1
38AP LVT
TERMINAL STRIP
–
+
4-20 mA
SIGNAL
GENERATOR
–
+
SAT (REQUIRED)
FS1
MAT/RAT (REQUIRED)
25
24
20
19
18
16
14
13
11
10
8
7
6
5
4
3
2
1
ALM
R
4-20 mA
SIGNAL
GENERATOR
–
+
TEMPERATURE
RESET
SIGNAL
9
LLSV-B (38APD)
LLSV-A2 (38APS)
or LLSV-B2 (065)
LLSV-A
or LLSV-B (065)
CXB-J6
(38APD070-130 ONLY)
FIELD-SUPPLIED
TRANSFORMER
(REQUIRED)
RED
7
6
5
PNK
ORN
LLSV-A2
LLSV-B2
24 VAC
SECONDARY
Fig. 141 — C.TYP=9 (VAV Setpoint) Wiring
LEGEND
NOTES:
1. Field wiring must be in accordance with local codes.
2. LVT-1 and 2 are for the alarm relay. The maximum load allowed for the alarm relay
is 5 VA sealed, 10 VA at 24 VAC. Field power supply is not required.
3. LVT-24, 25, and 2 are for control of field-supplied liquid line solenoid valve (LLSV)
15 VA sealed, 30 VA inrush at 24 VAC. Field power supply is not required.
4. For 38APD070-130 units, an additional LLSV, 15 VA sealed, 30 VA inrush at 24
VAC can be connected to CXB. A field-supplied control transformer is required, not
to exceed 75 VA.
5. All discrete inputs are 24 VAC.
6. Installation of fan status switch (FS1) is recommended. If not used, a jumper must
be installed.
7. Energy management module (EMM) is required.
8. The contacts for Remote On-Off, Fan Status Switch and Demand Limit must be
rated for dry circuit applications capable of handling a 24 VAC load up to 50 mA.
ALM R
—
Alarm Relay
CXB
—
Compressor Expansion Board
FS1
—
Fan Status Switch, AHU1
LLSV-A
—
Liquid Line Solenoid, Circuit A, First Stage
LLSV-A2
—
Liquid Line Solenoid, Circuit A, Second Stage (38APS040,050,
38APD070-130 only)
LLSV-B
—
Liquid Line Solenoid, Circuit B, First Stage (38APS065, 38APD only)
LLSV-B2
—
Liquid Line Solenoid, Circuit B, Second Stage (38APS065,
38APD070-130 only)
LVT
—
Low Voltage Terminal
MAT/RAT
—
Mixed Air Thermistor/Return Air Thermistor
SAT
—
Supply Air Thermistor
———
Factory Wiring
---------
Field Wiring