ENG
“FLSTDMAHUE” +030220961 - rel. 1.1 - 28.08.2019
21
5. MENU
DESCRIPTION
Press the
button to access the main menu. Select the category of parameters using UP/ DOWN and confirm by pressing Enter. If the password is required, enter
each figure using the i
/
buttons and confirm by pressing Enter. After a certain time, if no button is pressed, the password will need to be entered again.
Fig. 5.a
5.1 A.
On/Off Unit
There are two possible cases:
•
if time bands are disabled (C.Clock/scheduler
Î
C02.Enable scheduler),
the unit can only be switched on from the keypad in Comfort mode. The
temperature and humidity set points defined for this mode will then be
used indefinitely for control. (B.Setpoint
Î
B02.Comfort);
•
if time bands are enabled, the unit will be able to follow the time band
settings if “Auto” is selected (A.On/Off Unit
Î
A01.Auto). On the display, in
the special area, the operating mode will be determined by the time band
setting (C02) and preceded by the prefix “Auto”. If a different operating
mode is selected, the unit switches to manual mode.
On-Off Unità A01
On-Off Unità
AUTO
Fig. 5.b
14:33 23/08/10 U:01
0,
TR
iP
: 14.2°C
Umidità ripresa: 37%rH
Stato:
Auto-Econ
Fig. 5.c
Note:
see the “Functions” chapter for the complete description of the
On/Off function.
Manual mode
If time bands are enabled (C.Clock/scheduler
Î
C02.Enable scheduler), and
the unit is started from the keypad (A01.On/Off Unit), the following operating
modes can be selected:
1.
Auto: see previous paragraph;
2.
Manual mode: the unit is forced to operate in one of the available
operating modes (OFF, Economy, Pre-comfort, Comfort), for a time
ranging from 30 minutes to 8 hours. Automatic operation can resume
after this period by enabling reset (A.On/Off Unit
Î
Enable auto-resume).
Naturally the temperature and humidity set points must have previously
been set in the corresponding menu (B02.Setpoint
Î
Comfort; B03.
Setpoint
Î
Pre-comfort; B04.Setpoint
Î
Economy).
The display shows the operating mode in the relevant area, e.g. Comfort..
14:33 23/08/10 U:01
0,
TR
iP
: 14.2°C
Umidità ripresa: 37%rH
Stato:
Comfort
Fig. 5.d
5.2 B.
Setpoint
The first screen B01 displays the current temperature and humidity set points.
The temperature set point displayed considers any set point compensation
function operating (see the “Functions” chapter). If time bands are enabled
(C: Clock/scheduler
Î
C02: Enable scheduler), different temperature and
humidity set points can be set for Economy, Pre-comfort and Comfort modes
(B: Setpoint
Î
Comfort, Pre-comf, Economy) according to the season, summer
or winter. In total, then, 6 temperature set points and 6 humidity set points can
be set (screens B02, B03, B04). If time bands are not enabled, only the set point
for comfort mode can be set.