ENG
“FLSTDMAHUE” +030220961 - rel. 1.1 - 28.08.2019
8
Outdoor sensors
(Technical l050001790)
P/N
Type
Range
DPUT011000 Temperature -50T90°C, resistive output NTC 10kΩ@25°C
DPUC110000 Temperature -35T80°C, resistive output NTC 10kΩ@25°C & 4-20 mA
Humidity
10 to 90 RH, 4 to 20 mA output
NTC temperature sensors
(030220655)
P/N Type
Range
NTC*HP*
10 kΩ±1%@25 °C, IP67
-50…105/50°C (air / fluid)
NTC*WF*
10 kΩ±1%@25 °C (Fast), IP67
-50…105°C (fast)
NTC*WHP*
10 kΩ±1%@25 °C, IP68
-50…105°C
NTC*HF*
10 kΩ±1%@25 °C,strap-on, IP67
-50…90°C 105°C
NTC*WS*
10 kΩ±1%@25 °C, IP67
-40…105°C
PT1000 temperature sensors
(030220655)
P/N Type
Range
PT1*HP*
IP67
-50…105/50°C (air/ fluid)
PT1*WF*
IP67
-50…105°C
PT1*WP*
IP67
-50…105°C
PT1*HT*
IP67
-50…250°C
PT1*HF*
IP67, strap on
-50…105°C
Room air quality sensors
(Technical l050001300)
DPWQ* DPDQ*
CO
2
Sensors
P/N
Range
Output
DPWQ402000
0…2000 ppm
0…10 V
DPDQ402000
0…2000 ppm
0…10 V
CO
2
and VOC Sensors
P/N
Range
Output
CO
2
VOC
DPWQ502000
0…2000 ppm
0…100 %
0…10 V, 0…10 V
DPDQ502000
0…2000 ppm
0…100 %
0…10 V, 0…10 V
Differential air pressure sensors
(Technical l050000651)
P/N Range
Output
SPKD00U5N0
0...1000 Pa; 0...2500 Pa; 0...3000 Pa; 0...5000 Pa
4...20 mA
SPKD00C5N0
-50...+50 Pa; -100...+100 Pa; 0...+50 Pa; 0...+100 Pa
4...20 mA
Differential air pressure switches/flow switches
(
Technical leaflet
+050000645/ +050000647)
Pressure switches
P/N Range
Output
DCPD000100
0.5…5 mbar
ON/OFF
DCPD001100
0.2…2 mbar
ON/OFF
Flow switches
P/N Range
Output
DCFL000100
1…9 m/s
ON/OFF
Smoke and fire sensors
(Technical l050000520)
P/N Type
Output
SFFS000000
Smoke detector, 24 Vdc PS
ON/OFF
SFFF000000
Fire detector, 24 Vdc PS
ON/OFF
USB /RS485 converter code CVSTDUTLF0/ CVSTDUMOR0
(Technical l050000590)
CVSTDUTLFO CVSTDUMOR0
The USB/RS485 converter code CVSTDUTLF0 is used to connect a personal
computer running the pCO Manager program to the pLAN port (J10) on the
pCO controller, via a telephone connector. Alternatively, the CVSTDUMOR0
converter can be connected to other ports (figure).
Once the connection has been made, the application program software can
be loaded and the parameters set. See chapters “Software installation” and
”Appendix”.
CVS
T
DU
T
LF0
POWER
SUPPL
Y
USB
-
RS485
c
onverter
USB
C1
NO1
NO2
NO3
C1
C4
NO4
NO5
NO6
C4
C7
NO7
C7
NO8
C8
NC8
G
G0
U1
u2
GND
+VDC
+V
term
GND
+5 V
REF
U4
GND
U5
GND
VG
VG0
Y1
Y2
Y3
Y4
ID
1
ID
2
ID
3
ID
4
ID
5
ID
6
ID
7
ID
8
IDC1
J1
J10
FieldBus card
B M S card
input: 24 V 50...60 Hz / 28...36 V
max. power: 45 VA/20 W
CANL
CANH
GND
OFF
4 3
2
1
ON
J 2 5
B M S2
CVS
T
DUMOR0
CVS
T
DUMOR0
pCO
Manager
c
onnessioni
in
a
l
ternativa
a
l
ternative
c
onne
c
tions
Fig. 1.a
Summary of Contents for FLSTDMAHUE
Page 2: ......
Page 4: ......
Page 91: ...ENG FLSTDMAHUE 030220961 rel 1 1 28 08 2019 91 ...
Page 92: ...ENG FLSTDMAHUE 030220961 rel 1 1 28 08 2019 92 ...
Page 93: ......