ENG
“FLSTDMAHUE” +030220961 - rel. 1.1 - 28.08.2019
83
Modbus
ADDR
Carel
ADDR.
Screen
index
Commissioning Tool variable name
Description
Def.
UOM
Min
Max
R/W
323
115
Gfc21
Cascade.Thr_Start_Rec_Heat
Heating coil control starting point
40
%
0
100
R/W
324
116
Gfc22
Cascade.Thr_Start_Heat_PostHeat
Reheating coil control starting point
80
%
0
100
R/W
325
117
Gfc23
COOLING.CutOff_Cool
Cooling valve cut-off in cooling
0
%
0
100
R/W
326
118
Gfc23
COOLING.CutOff_Dehum
Cooling valve cut-off in dehumidify
0
%
0
100
R/W
327
119
Gfc24
PREHEATING.CutOff_PreH
Preheating valve cut-off
0
%
0
100
R/W
328
120
Gfc29
REHEATING.CutOff_PostH
Reheating valve cut-off
0
%
0
100
R/W
329
121
Gfc26
COOL_HEAT_COIL.CutOff_Cool
Cool/heat valve cut-off in cooling.
0
%
0
100
R/W
330
122
Gfc26
COOL_HEAT_COIL.CutOff_Dehum
Cool/heat valve cut-off in dehumidify
0
%
0
100
R/W
331
123
Gfc26
COOL_HEAT_COIL.CutOff_Heat
Cool/heat valve cut-off in heating.
0
%
0
100
R/W
332
124
Gfc30
AIR_QUALITY.Setp_Reg_CO2
Air quality set point in ppm of CO2
1200
ppm
0
5000
R/W
333
125
Gfc30
AIR_QUALITY.Setp_Reg_VOC
Air quality set point in % of VOC
50
%
0
100
R/W
334
126
Gfc30
AIR_QUALITY.Diff_Reg_CO2
Air quality differential in ppm of CO2
200
ppm
0
2000
R/W
335
127
Gfc30
AIR_QUALITY.Diff_Reg_VOC
Air quality differential in % of VOC
10
%
0
100
R/W
336
128
Gfc32
Recovery.Defrost_Speed
Heat wheel speed in defrost
100
rpm
0
100
R/W
337
129
Gfc36
Reg_Loop_1.Gen_Reg_Int_Time
Generic loop 1 integral time
0
s
0
999
R/W
338
130
Gfc37
Reg_Loop_2.Gen_Reg_Int_Time
Generic loop 2 integral time
0
s
0
999
R/W
339
131
Gfc38
Reg_Loop_3.Gen_Reg_Int_Time
Generic loop 3 integral time
0
s
0
999
R/W
340
132
Gfc39
Reg_Loop_4.Gen_Reg_Int_Time
Generic loop 4 integral time
0
s
0
999
R/W
341
133
SCHEDULER.Season_Sel_From
Select season from BMS/ID
4
-
0
4
R/W
342
134
SCHEDULER.S_Start_Day
Summer start day
15
day
1
31
R/W
343
135
SCHEDULER.S_Start_Month
Summer start month
5
month
1
12
R/W
344
136
SCHEDULER.W_Start_Day
Winter start day
30
day
1
31
R/W
345
137
SCHEDULER.W_Start_Month
Winter start month
9
month
1
12
R/W
346
138
SCHEDULER.S_W_Delay_Auto_Change
Summer/Winter season changeover delay
1
Hour
0
999
R/W
347
139
Force_Supply_Fan
Force supply fan (0=Auto, 1=000%...101=100%)
0
%
0
101
R/W
348
140
Force_Return_Fan
Force return fan (0=Auto, 1=000%...101=100%)
0
%
0
101
R/W
349
141
Force_Cooling
Force cooling coil(0=Auto, 1=000%...101=100%)
0
%
0
101
R/W
350
142
Force_PreHeating
Force preheating coil (0=Auto, 1=000%...101=100%)
0
%
0
101
R/W
351
143
Force_PostHeating
Force reheating coil (0=Auto, 1=000%...101=100%)
0
%
0
101
R/W
352
144
Force_Heat_Cool
Force heating/cooling coil (0=Auto, 1=000%...101=100%)
0
%
0
101
R/W
353
145
Force_Humidifier
Force humidifier (0=Auto, 1=000%...101=100%)
0
%
0
101
R/W
354
146
Hour_Supply_Fan_1
Supply fan 1 operating hours (X1000) - thousands
-
-
0
999
R
355
147
Hour_L_Supply_Fan_1
Supply fan 1 operating hours
-
Hour
0
999
R
356
148
Hour_Supply_Fan_2
Supply fan 2 operating hours (X1000) - thousands
-
-
0
999
R
357
149
Hour_L_Supply_Fan_2
Supply fan 2 operating hours
-
Hour
0
999
R
358
150
Hour_Return_Fan_1
Return fan 1 operating hours (X1000) - thousands
-
-
0
999
R
359
151
Hour_L_Return_Fan_1
Return fan 1 operating hours
-
Hour
0
999
R
360
152
Hour_Return_Fan_2
Return fan 2 operating hours (X1000) - thousands
-
-
0
999
R
361
153
Hour_L_Return_Fan_2
Return fan 2 operating hours
-
Hour
0
999
R
362
154
Hour_Humidifier
Humidifier operating hours (X1000) - thousands
-
-
0
999
R
363
155
Hour_L_Humidifier
Humidifier operating hours
-
Hour
0
999
R
364
156
Hour_Rotary_Recovery
Heat wheel operating hours (X1000) - thousands
-
-
0
999
R
365
157
Hour_L_Rotary_Recovery
Heat wheel operating hours
-
Hour
0
999
R
366
158
Hour_Cool_Pump_1
Cooling coil pump 1 operating hours (X1000) - thousands
-
-
0
999
R
367
159
Hour_L_Cool_Pump_1
Cooling coil pump 1 operating hours
-
Hour
0
999
R
368
160
Hour_Cool_Pump_2
Cooling coil pump 2 operating hours (X1000) - thousands
-
-
0
999
R
369
161
Hour_L_Cool_Pump_2
Cooling coil pump 2 operating hours
-
Hour
0
999
R
370
162
Hour_PreH_Pump_1
Preheating coil pump 1 operating hours (X1000) - thousands
-
-
0
999
R
371
163
Hour_L_PreH_Pump_1
Preheating coil pump 1 operating hours
-
Hour
0
999
R
372
164
Hour_PreH_Pump_2
Preheating coil pump 2 operating hours (X1000) - thousands
-
-
0
999
R
373
165
Hour_L_PreH_Pump_2
Preheating coil pump 2 operating hours
-
Hour
0
999
R
374
166
Hour_PostH_Pump_1
Reheating coil pump 1 operating hours (X1000) - thousands
-
-
0
999
R
375
167
Hour_L_PostH_Pump_1
Reheating coil pump 1 operating hours
-
Hour
0
999
R
376
168
Hour_PostH_Pump_2
Reheating coil pump 2 operating hours (X1000) - thousands
-
-
0
999
R
377
169
Hour_L_PostH_Pump_2
Reheating coil pump 2 operating hours
-
Hour
0
999
R
378
170
Hour_Heaters_Pre_1
Preheating heater 1 operating hours (X1000) - thousands
-
-
0
999
R
379
171
Hour_L_Heaters_Pre_1
Preheating heater 1 operating hours
-
Hour
0
999
R
380
172
Hour_Heaters_Pre_2
Preheating heater 2 operating hours (X1000) - thousands
-
-
0
999
R
381
173
Hour_L_Heaters_Pre_2
Preheating heater 2 operating hours
-
Hour
0
999
R
382
174
Hour_Heaters_Pre_3
Preheating heater 3 operating hours (X1000) - thousands
-
-
0
999
R
383
175
Hour_L_Heaters_Pre_3
Preheating heater 3 operating hours
-
Hour
0
999
R
384
176
Hour_Heaters_Pre_4
Preheating heater 4operating hours (X1000) - thousands
-
-
0
999
R
385
177
Hour_L_Heaters_Pre_4
Preheating heater 4 operating hours
-
Hour
0
999
R
386
178
Hour_Heaters_Post_1
Reheating heater 1 operating hours (X1000) - thousands
-
-
0
999
R
387
179
Hour_L_Heaters_Post_1
Reheating heater 1 operating hours
-
Hour
0
999
R
388
180
Hour_Heaters_Post_2
Reheating heater 2 operating hours (X1000) - thousands
-
-
0
999
R
389
181
Hour_L_Heaters_Post_2
Reheating heater 2 operating hours
-
Hour
0
999
R
390
182
Hour_Heaters_Post_3
Reheating heater 3 operating hours (X1000) - thousands
-
-
0
999
R
391
183
Hour_L_Heaters_Post_3
Reheating heater 3 operating hours
-
Hour
0
999
R
392
184
Hour_Heaters_Post_4
Reheating heater 4operating hours (X1000) - thousands
-
-
0
999
R
393
185
Hour_L_Heaters_Post_4
Reheating heater 4 operating hours
-
Hour
0
999
R
394
186
Unit_Status
Unit status
-
-
0
17
R/W
396
187
OffCoil_Hum
Humidity downstream of coils
-
-
0
100
R/W
397
188
Force_Cooling_Ana
Force cooling coil analogue output
-
-
0
100
R/W
398
189
Force_PreHeating_Ana
Force preheating heater analogue output
-
-
0
100
R/W
399
190
Force_PostHeating_Ana
Force reheating heater analogue output
-
-
0
100
R/W
400
191
Force_Humid_Reg_Req_Ana
Force humidity request
-
-
0
100
R/W
401
192
Gfb23
Msk_OffCoil_Hum
Humidity probe value downstream of coils
-
%RH
0
1000
R
402
193
IEC_Limit_Probe
IEC limit probe (humidity)
-
%RH
0
1000
R
403
194
Gfb24
Msk_IEC_Limit_Probe
IEC limit probe value (humidity)
-
%RH
0
1000
R
404
195
Gfc14
Temp_Hum_Priority
Priority, temperature or humidity
2
-
0
2
R/W
405
196
Gfc01
Main_Info_1st_Sel
Variable 1 on display
7
-
0
16
R/W
405
197
Gfc01
Main_Info_2st_Sel
Variable 2 on display
7
-
0
16
R/W
406
198
Gfc05a
Cool_Heat_Delay
Summer/winter changeover delay
10
min
0
999
R/W
407
199
Gfc12a
Humid_Dehumid_Delay
Humidification/dehumidification changeover delay
10
min
0
999
R/W
408
200
Gfc13
HUMID_REG.Setp_Sum_H_Lim
Supply humidity limits: summer high
80
%RH
0
100
R/W
409
201
Gfc13
HUMID_REG.Setp_Sum_L_Lim
Supply humidity limits: summer low
20
%RH
0
100
R/W
410
202
HUMID_REG.Setp_Sum_AbsHum_H_Lim
Supply absolute (specific) humidity limits: summer high
15
g/Kg
0
100
R/W
411
203
HUMID_REG.Setp_Win_AbsHum_H_Lim
Supply absolute (specific) humidity limits: winter high
15
g/Kg
0
100
R/W
412
204
HUMID_REG.Setp_Sum_AbsHum_L_Lim
Supply absolute (specific) humidity limits: summer low
5
g/Kg
0
100
R/W
413
205
HUMID_REG.Setp_Win_AbsHum_L_Lim
Supply absolute (specific) humidity limits: winter low
5
g/Kg
0
100
R/W
414
206
HUMID_REG.Diff_Lim_AbsHum
Supply limit differential
0
g/Kg
0
100
R/W
415
207
HUMID_REG.Int_Limit_Time_AbsHum
Supply limit integral time
0
s
0
999
R/W
416*
Gfc18
FANS.DeadBand_Press_Sup
Supply pressure neutral zone
0
Pa
0
2000
R/W
417*
Gfc19
FANS.DeadBand_Press_Ret
Return pressure neutral zone
0
Pa
0
2000
R/W
418*
ComfortSetp_AirFlow_Sup
Supply flow set point in Comfort (x 100 m3/h)
200
-
0
32767
R/W
419*
PreComfSetp_AirFlow_Sup
Supply flow set point in Pre-comfort (x 100 m3/h)
200
-
0
32767
R/W
Summary of Contents for FLSTDMAHUE