ENG
“FLSTDMAHUE” +030220961 - rel. 1.1 - 28.08.2019
74
Screen
Display description
Description/notes
Def.
UOM
Min
Max
Value description
Type
R/W
Carel addr.
Hc07a
Damper limit switch alarm
delay
Enable: Hc03a
10
s
0
999
I
R/W
-
Hc07b
Coefficient for flow-rate
calculation
Enable: Ha03
Supply K
0
-
0
5000
I
R/W
-
Return K
0
-
0
5000
I
R/W
-
Hc07c
Frost protection alarm delay
with heaters
Enable: (Ha05) min 1
preheating heater and
output assigned
120
s
0
600
I
R/W
-
Hc08
Floating valve travel time
180
s
1
3200
I
R/W
-
Hc09
Enable preheating coil water temp. threshold
No
-
No
Yes
0:No¦1:Yes
I
R/W
-
Setpoint
25
°C
-99.9
99.9
A
R/W
-
Differential
2
°C
0
9,
A
R/W
-
Hc10
Cooling coil
Floating valve travel time
180
s
1
3200
I
R/W
-
Hc11
Enable cooling coil water temperature threshold
No
-
No
Yes
0:No¦1:Yes
D
R/W
-
Setpoint
35
°C
-99.9
99.9
A
R/W
-
Differential
2
°C
0
9.9
A
R/W
-
Hc12
Delay between cooling/heating change
10
min
0
999
I
R/W
-
Hc13
Heating/cooling coil
Floating valve travel time
180
s
1
3200
I
R/W
-
Hc14
Enable heating/cooling coil input limit
No
-
No
Yes
0:No¦1:Yes
D
R/W
-
Hot threshold
25
°C
0
99.9
A
R/W
-
Cool threshold
35
°C
0
99.9
A
R/W
-
Differential
2
°C
0
9.9
A
R/W
-
Hc15
Reheating coil
Floating valve travel time
180
s
0
3200
I
R/W
-
Hc16
Enable reheating coil water temperature threshold
No
-
0:No¦1:Yes
D
R/W
-
Setpoint
25
°C
-99,
99,
A
R/W
-
Differential
2
°C
0
9,
A
R/W
-
Hc17
Pumps
Flow alarm delay
Start
30
s
1
999
I
R
-
Steady operation
15
s
1
999
I
R
-
Rotation time
96
Hour
0
999
I
R/W
-
Overlapping time
0
s
-99
99
I
R/W
-
Hc18
Heat recovery unit
Frost protection delay
Start
120
s
0
999
I
R/W
-
End
60
s
0
999
I
R/W
-
Clogged alarm delay
60
s
0
300
I
R/W
-
Hc18a
IEC air flow limit
Maximum
0
%
0
100
I
R/W
-
Hc19
Air quality
Integral time
300
s
0
9999
I
R/W
-
Cleaning time
10
min
0
300
I
R/W
-
Hc20
Generic alarm input delay
0
s
0
9999
I
R/W
-
Disable buzzer
No
-
-
-
0:No¦1:Yes
D
R/W
-
Enable clock board
No
-
-
-
0:No¦1:Yes
D
R/W
-
Hc40
Supply VFD
Volt at 0 Hz
0
%
0
40
A
R/W
-
Switch frequency
0
kHz
1
16
A
R/W
-
V/f curve midpoint
Voltage
0
%
0
100
A
R/W
-
Frequency
0
Hz
0
320
A
R/W
-
Hc41
Supply VFD
V/f ratio
Linear
0:Linear ¦ 1:Squared ¦ 2:Programmable
¦ 3:Linear with flux optimisation
I
R/W
-
V/f Optimisation
Not used
0:Not used ¦ 1:Automatic boost
I
R/W
-
Auto restart
Not used
0:Not used ¦ 1:used
I
R/W
-
Hc42
Supply VFD
Min frequency
0
Hz
0
Max freq.
A
R/W
-
Max frequency
50
Hz
Min freq.
320
A
R/W
-
Acceleration time
1
s
0.1
3200
A
R/W
-
Deceleration time
1
s
0.1
3200
A
R/W
-
Hc50
Return VFD
Volt at 0 Hz
0
%
0
40
A
R/W
-
Switch frequency
0
kHz
1
16
A
R/W
-
V/f curve midpoint
Voltage
0
%
0
100
A
R/W
-
Frequency
0
Hz
0
320
A
R/W
-
Hc51
Return VFD
V/f ratio
Linear
0:Linear ¦ 1:Squared ¦ 2:Programmable
¦ 3:Linear with flux optimisation
I
R/W
-
V/f Optimisation
Not used
0:Not used ¦ 1:Automatic boost
I
R/W
-
Auto restart
Not used
0:Not used ¦ 1:used
I
R/W
-
Hc52
Return VFD
Min frequency
0
Hz
0
Max freq.
A
R/W
-
Max frequency
50
Hz
Min freq.
320
A
R/W
-
Acceleration time
1
s
0.1
3200
A
R/W
-
Deceleration time
1
s
0.1
3200
A
R/W
-
d. Initialisation
Hd01
Save configuration
No
-
No
Yes
0:No¦1:Yes
D
R/W
-
Hd02
Default installation
Erase user settings and install global default values
No
-
-
-
0:No¦1:Yes
I
R/W
-
Hd03
Insert new manufacture
password (PW2)
1234
-
0
9999
I
R/W
-
e. Input/output test
He01
Digital output
Supply fan
Auto
-
Auto
On
0:Auto ¦ 1:Off ¦ 2:On
I
R/W
-
Supply fan 2
Auto
-
Auto
On
0:Auto ¦ 1:Off ¦ 2:On
I
R/W
-
Return fan
Auto
-
Auto
On
0:Auto ¦ 1:Off ¦ 2:On
I
R/W
-
Return fan 2
Auto
-
Auto
On
0:Auto ¦ 1:Off ¦ 2:On
I
R/W
-
Summary of Contents for FLSTDMAHUE