ENG
“FLSTDMAHUE” +030220961 - rel. 1.1 - 28.08.2019
51
On/Off fans with direct and star
-
delta starting
The fans are started when the unit is powered up. For starting, as well as the
fan outputs, the outputs for the 3 contactors also need to be enabled (see
the figure)
1.
Supply/return air fan line (K1)
2.
Supply/return air fan star (K3);
3.
Supply/return air fan delta (K2)
The switching delay time also needs to be set.
M
3~
K1
K2
K3
L3
L1
L2
Fig. 9.p
Screen index
Display description
Selection
Ha03
Fan type
1: On-Off(direct start) ¦ 2: On-Off(star-delta)
¦ 3: On-Off (double) ¦ 4: Inverter ¦ 5: On-Off(2
speed) ¦ 6: On-Off (duty standby) ¦
Hb37
Star-delta logic
Supply fan line
position ≠0
Supply fan star
position ≠0
Supply fan delta
position ≠0
Hb37
Return fan line
position ≠0
Return fan star
position ≠0
Return fan delta
position ≠0
Screen index
Display description
Def
Min
Max
UOM
Hc04
Fans Star-Delta timing
Star-line
-
0
99
ms
Star
-
0
99
ms
Star-delta
-
0
99
ms
ON
OFF
ON
OFF
t
K1
d1
REQ
ON
OFF
ON
OFF
K3
K2
d2
d3
Fig. 9.q
Key
REQ
Fan request
K1
Fan line
K2
Fan delta
K3
Fan star
d1
Line – star delay
d2
Star-delta delay
d3
Star time
Double On/Off fans
This is when there are two fans fitted in parallel, to modify the ventilating
section. Activation again depends on unit power-on, however a delay is
available between activation of the first and second fan (supply – return).
Screen index
Display description
Def
Min
Max
UOM
Hc06
Fans timing
Stop delay
30
0
999
s
Supply-return
0
0
999
s
Fans with inverters
If the fans are controlled by inverter, three types of control can be selected:
Screen index
Display description
Selection
Ha03
TYpe of control
1: Static pressure ¦ 2: Air quality
¦ 3: Fixed speed ¦ 4: Air flow-rate
1.
Constant pressure/flow-rate: at unit power-on, the fan will operate
at minimum speed and subsequently will try to reach the differential
pressure/flow-rate set point, using the PID parameter settings. The values
are converted using the formula shown in the figure, once the value of
coefficient K has been set. The set point can be selected as pressure or
flow-rate, according to the formula shown in the figure. The flow-rate
setting allows a different set point to be selected in pre-comfort, comfort
and economy modes.
∆
p
V
= k
∆
p
.
V
=
p
ort
a
t
a
/
flow r
a
te
p
=
p
ressione/
p
ressure
.
Fig. 9.r
Screen
index
Display description
Def
Min
Max
UOM
Hc07b
Coefficient for calculating the
flow-rate
Supply K
0
0
5000
-
Return K
0
0
5000
-
Gfc17
Supply fan inverter
Minimum/fixed power
30
0
100
%
Maximum power
100
0
100
%
Return fan inverter
%
Minimum/fixed power
30
0
100
%
Maximum power
100
0
100
%
Gfc18
Supply fan inverter flow
Set point
1500
0
Max supply press.
diff. limit
Pa
Differential
300
0
1000
Pa
Integral time
300
0
1000
s
Derivative time
10
0
9999
s
Gfc19
Return fan inverter flow
Set point
1500
0
Max return press.
diff. limit
Pa
Differential
300
0
1000
Pa
Integral time
300
0
1000
s
Derivative time
10
0
9999
s
Gfc19a
Supply flow control set point
Comfort:
20000
0
3276700
m
3
/h
Pre-comfort:
20000
0
3276700
m
3
/h
Economy:
20000
0
3276700
m
3
/h
Gfc19b
Return flow control set point
Comfort:
20000
0
3276700
m
3
/h
Pre-comfort:
20000
0
3276700
m
3
/h
Economy:
20000
0
3276700
m
3
/h
Gfc19c
Supply air flow control
Differential
1000
0
3276700
m
3
/h
Integral time
300
0
9999
s
Derivative time
10
0
9999
s
Neutral zone
500
0
200000
m
3
/h