Example 2:
overlapping of preheating and reheating coils.
100%
0%
Heating
Free_heat/
Reheat
Device_opening
recovery
50%
66%
100%
Req
33%
Preheat
Key
Recovery
Recovery
Req
Request
Free_heat
Freeheating
Device_opening
Device activation
Preheat
Preheating coil valve Reheat
Reheating coil valve
9.11 Supply limits
Definition
Note
: the supply limits function can be activated (Gfc04) only if the
control probe is the return probe or room probe .
The algorithm is used to correct the action of the main control function to
return within acceptable values for the supply temperature. For example,
if the fresh air damper opens to satisfy a air quality request, this attenuates
the request on the actuators (e.g. heating coil, humidifier) so as to mitigate
the effect on the supply temperature and humidity. Without this function,
the supply air may cause discomfort (e.g. too hot or too cold) near the air
inlets. The function can be activated on either the minimum or maximum
temperature or humidity. There are two possible cases: action concordant
with or contrasting against control.
Temperature limits with concordant action
Example of operation in heating mode (winter):
when the control set point
is reached and the heating coil stops heating, an air quality request causes
the fresh air damper to open and consequently the air supply temperature
decreases. To prevent the temperature measured by the control probe from
changing further, when the air supply temperature is less than minimum
allowed limit the heating coil is activated, with proportional or PI control,
according to the following graph, where the total request is 50%.
100%
0%
Req_heat
Reg_temp
Set
NZ_heat
diff_heat
100%
0%
Req_lim_heat
Supply_temp
Low_limit_temp
diff
50%
0 % + 5 0 % = 5 0 %
Key
Req_lim_ heat Additional heating
request
Reg_temp
Control probe
temperature
NZ_heat
Neutral zone in heating
Supply_temp Supply probe
temperature
Diff_heat
Heating differential
Diff
Supply limit differential
The behaviour is similar in cooling mode (summer).
100%
0%
Req_cool
Reg_temp
diff_cool
NZ_cool
100%
0%
Req_lim_cool
Supply_temp
diff
High_limit_temp
50%
0 % + 5 0 % = 5 0 %
Key
Req_lim_cool
Additional cooling
request
Reg_temp
Control probe
temperature
NZ_cool
Neutral zone in cooling
Supply_temp
Supply probe tempe-
rature
Diff_cool
Cooling differential
Diff
Supply limit
differential
High_limit_ temp High temperature limit
Screen index
Display description
Selection
Gfc04
Temperature regulation
Auto cool/heat
No ¦ Yes
Supply limits
None ¦ High ¦ Low ¦
High/low
Alto/basso
Screen index
Display description
Def
Min
Max
UOM
Gfc07
Temperature supply limits
Summer high
40
-99.9
99.9
°C
Winter high
40
-99.9
99.9
°C
Summer low
10
-99.9
99.9
°C
Winter low
10
-99.9
99.9
°C
Differential
3
0
99.9
°C
Integral time
150
0
999
s
Humidity limits with concordant action
Example of operation in humidification mode: when the control set point
is reached and humidification ends, an air quality request causes the fresh
air damper to open and consequently the supply humidity may decrease.
To prevent the humidity measured by the control probe from changing
further, when the supply air humidity is less than minimum allowed limit,
the humidifier is activated, with proportional or PI control, according to the
following graph, where the total request is 50%.
100%
0%
Req_hum
Reg_hum
Set
NZ_hum
diff_hum
100%
0%
Req_lim_hum
Supply_hum
Low_limit_hum
diff
50%
0 % + 5 0 % = 5 0 %
Key
Req_lim_hum
Additional
humidification request
Reg_hum
Control probe
humidity
NZ_hum
Neutral zone in
humidification
Supply_hum
Supply probe
humidity
Diff_hum
Humidification
differential
Diff
Supply limit
differential
Low_limit_hum
Low humidity limit
The behaviour is similar in dehumidification mode
100%
0%
Req_dehum
Reg_hum
diff_dehum
NZ_dehum
100%
0%
Req_lim_dehum
Supply_hum
diff
High_limit_hum
50%
0 % + 5 0 % = 5 0 %
Key
Req_lim_dehum
Dehumidification
request for limit
Reg_hum
Control probe
humidity
NZ_dehum
Neutral zone in
dehumidification
Supply_hum
Supply probe
humidity
Diff_dehum
Dehumidification
differential
Diff
Supply limit
differential
High_limit_hum
High humidity limit
Screen index Display description
Selection
Gfc10
Humidity regulation
Auto hum/dehum
No ¦ Yes
Supply limits
None ¦ High ¦ Low ¦
High/low