8400-M022-O1 Rev K
Model 190 Indicator
34
Cont1=
(Continuous Output on Serial Interface)
Press the
TARE
key to show the current setting. If the setting displayed is acceptable,
press the
TARE
key again to save it.
Otherwise, use the
Fn/
key to toggle the setting and press the
TARE
key to save it.
Cont1=YES
Cont1=No
Continuous Output on Serial Interface
No Continuous Output on Serial Interface
If
Cont1=YES
(Continuous Output) is selected, an additional prompt,
tYPE=
will be
displayed.
If
Cont1=no
(No Continuous Output) is selected, proceed to the Weight-On- Demand
section.
tyPE=
(Continuous Output Format)
Press the
TARE
key to show the current setting. If the setting displayed is acceptable,
press the
TARE
key again to save it.
Otherwise, use the
Fn/
key to toggle the setting and press the
TARE
key to save it.
0 = Continuous Output uses SMA format
1 = Continuous Output uses Cardinal Scoreboard format
SMA Continuous Output Format
If SMA is selected, data will be transmitted in the following format:
<lf><s><r><n><m><f><xxxxxx.xxx><uuu><cr>
Where:
lf
= Line Feed
s
= Flags
Z= center of Zero, O = Overcap, E = zero Error,
e = weight not currently being displayed
r
= Range
1 (
always a 1
)
n
= Mode
G = Gross, T = Tare, N = Net
m
= Motion
M = Motion, " "(
blank
) = no motion
f
= Custom
Custom flag
xxxxxx.xxx = Weight
Ten characters including a decimal point (if any)
uuu
= Units
lb, oz, kg, g
cr
= Carriage Return (hex 0D)