ELECTRICAL CONNECTION

•  Before connecting the appliance make sure that the voltage and frequency rated on the data plate conform 

to those of the mains supply. 

 

WARNING!

 A double pole trip switch with a least 

3 mm

 between the contacts must be installed between the 

unit and the mains supply.

•  Connect the control and security device wires.

•  Connect the power supply cable to the device.

•  Do not use cables with aluminium conductors; do not solder the ends of cables which are to be inserted into 

the binding posts; use cables which are marked 

T min 85°C

 and are resistant to atmospheric agents.

•  The terminal wires must be positioned in such a way that both the wire and the insulating sheath are tightly 

fastened (plastic binding is sufficient).

Terminal board connections 

1-2 

Programmer power supply 

230 Vac

3-4-5 

Motor command output Closing-Opening-Common

6-7 

Power supply/motor earth binding posts 

8-9 

24 Vac 7 W

 output, powering external devices

10  

TA

 (NO contact) opening button input

11 

TC

 (NO contact) closing button input

12-13 

CMN

 common for all inputs and outputs 

14  

TB

 (NC contact) blocking button input 

15 

CSP

 (NC contact) safety edge input. Opening this contact will provoke a travel direction inversion during 

the closing stage and block movement during the opening stage (movement will continue the next time 

a command is given). 

16 

FTC 

(NC contact) security device input ( inverting photocells during closing). The opening of this contact 

will provoke a travel direction inversion during closure due to the cutting in of the safety device.

17 

CSP_A

 analogical safety edge input (

8.2 k

)

18 

ANEM

 anemometer input (see anemometer functions on page 11)

19 

Mass for radio receiver antenna

20 

Radio receiver antenna pole

ALL UNUSED NC CONTACTS MUST BE BRIDGED
Power up the circuit and make sure that the indicator LEDs are in the following condition:

-

  L 

Green power on LED  

ON

-  L2 

Red transmitter code management LED 

OFF

-  L3 

Red time programming LED 

OFF

If the green power on 

LED "L"

 does 

not light up

 check the condition of the fuses and the power cable contacts 

at binding posts

 

1-2 (fig.1).

Setting the torque limiter

The torque can be set to minimum, seeing as the appliance will give a maximum power thrust each time it receives 

a movement command 

Position 

"

MIN

equals: 

20 Vac

Position 

"

A

equals: 

45 Vac

Position 

"

B

equals: 

70 Vac

Position 

"

C

equals: 

95 Vac

Position 

"

MAX

"  equals:  

230 Vac 

To set the dip-switches; turn off the power to the programmer, change the settings and then switch the 

power back on.

Jumper “REMOTE MEMO”

Inserted: 

memorization via radio enabled

Deactivated:  memorization via radio disabled

 

Jumper “SEL_FTC”

Inserted:  

the photocells will impede the activation of the motor if an alarm condition is present 

Deactivated:   the photocells function as a safety device only while the shutter is closing

Jumper “CSP_A ENABLE”

Inserted:  

analogical safety edge enabled

Deactivated:  analogical safety edge disabled

M I

N A

B C

M A

X

Summary of Contents for PRG304

Page 1: ...BASE Pagina 4 COLLEGAMENTO ELETTRICO Pagina 5 PROGRAMMAZIONE TEMPI Pagina 6 MODALIT DI FUNZIONAMENTO Pagina 6 COMANDO VIA RADIO Pagine 6 7 IMPORTANT REMARKS Page 8 TECHNICAL SPECIFICATIONS Page 8 MOTH...

Page 2: ...tt B LEGEND LP Warning lights FTC RX Photocell receiver FTC TX Photocell projector CSP Standard safety edge CSP_A Analogical safety edge 8 2 k Attention to use an analogical safety edge 8 2 k remember...

Page 3: ...icamente l integrit del cavo d alimentazione Se esso presenta segni di usura e o danneggiamento deve essere sostituito dal costruttore o dal suo servizio di assistenza tecnica CARATTERISTICHE TECNICHE...

Page 4: ...MDK RT MDK RTL 1 SCHEDA BASE Legenda F1 Fusibile 0 5 A rapido protezione sovraccarichi 24 Vac F2 Fusibile 3 15 A rapido protezione sovraccarichi 230 Vac D1 Dip switch selezione funzioni P1 Pulsante di...

Page 5: ...del contatto conseguente all intervento dei dispositivi di sicurezza durante la fase di chiusura attuer l inversione di moto 17 CSP_A ingresso costa sensibile analogica 8 2 k 18 ANEM ingresso anemomet...

Page 6: ...la funzione di comando sequenziale Apertura Stop Chiusura Stop Semiautomatico Dip 1 OFF Dip 2 ON richiusura automatica disabilitata i tasti canale del trasmettitore hanno la funzione A Apertura B Chi...

Page 7: ...n altro codice 4 Per uscire dalla modalit lasciare trascorrere 3 sec senza memorizzare codici il ricevitore emetter un bip lungo 5 sec ed uscir dalla modalit Quando la memoria viene completamente occu...

Page 8: ...or damage have it replaced by the manufacturer or an authorised after sales service technician TECHNICAL SPECIFICATIONS Power supply Vac 230 Frequency Hz 50 60 Overall power consumption W 650 Nominal...

Page 9: ...6 5 4 7 8 2 3 6 5 4 7 2 MDK RT MDK RTL 1 MOTHER BOARD Legend F1 0 5 A rapid action fuse overload protection 24 Vac circuit F2 3 15 A rapid action fuse overload protection 230 Vac circuit D1 Function...

Page 10: ...device input inverting photocells during closing The opening of this contact will provoke a travel direction inversion during closure due to the cutting in of the safety device 17 CSP_A analogical saf...

Page 11: ...reclosing deactivated the transmitter channels have the following functions A Open B Close C Stop D Sequential Automatic Dip 1 ON Dip 2 OFF automatic reclosing enabled the transmitter channels have th...

Page 12: ...f half a second each after which the receiver will be ready to receive another code 4 To leave the programming mode wait for 3 seconds without memorising any codes The receiver will sound a five secon...

Page 13: ...riodiquement l tat du c ble d alimentation S il pr sente des traces d usure et ou d en dommagement il doit tre remplac par le fabricant ou par son service d assistance technique CARACT RISTIQUES TECH...

Page 14: ...clature F1 Fusible 0 5 A rapide protection contre les surcharges 24 Vac F2 Fusible 3 15 A rapide protection contre les surcharges 230 Vac D1 Dip switch s lection des fonctions P1 Bouton de programmati...

Page 15: ...n des dispositifs de s curit durant la phase de fermeture provoquera une inversion de la man uvre 17 CSP_A entr e pour bord de protection analogique 8 2 k 18 ANEM entr e pour an mom tre voir fonctionn...

Page 16: ...entielle Ouverture Blocage Fermeture Blocage Semi automatique Dip 1 OFF Dip 2 ON refermeture automatique invalid e les touches de canal de l metteur sont affect es la fonction A Ouverture B Fermeture...

Page 17: ...s m moriser de codes Le r cepteur mettra un bip de 5 secondes et quittera le proc d Lorsque la m moire est pleine le buzzer met 10 bips tr s courts et on sort automatiquement du proc d de m morisation...

Page 18: ...gen Abst nden berpr ft werden Wenn daran Zeichen von Verschlei und oder Besch digungen erkennbar sind muss es vom Hersteller oder von dessen technischen Kundendienst ausgewechselt werden TECHNISCHE DA...

Page 19: ...EKTRONISCHE PLATINE Zeichenerkl rung F1 Sicherung 0 5 A flink berlastungsschutz 24 Vac F2 Sicherung 3 15 A flink berlastungsschutz 230 Vac D1 Dip Schalter Funktionenwahl P1 Taste zur Programmierung de...

Page 20: ...ktes infolge des Eingreifens der Sicherheitsvorrichtungen w hrend des Schlie ens verursacht die Bewegungsumkehrung 17 CSP_A N C Kontakt Eingang analogische Sicherheitsleiste 8 2 k 18 ANEM Eingang Wind...

Page 21: ...omatische Wiederverschlie ung abgeschaltet die Kanaltasten des Senders haben die Funktion A ffnen B Schlie en C Stop D Sequenziell Automatik Dip 1 ON Dip 2 OFF automatische Wiederverschlie ung eingesc...

Page 22: ...hern der Empf nger wird nun einen 5 Sek dauernden Bip Ton abgeben und aus dem Speichermodus austreten Wenn der Speicher vollkommen belegt ist l sst der Summer 10 Bip T ne in rascher Folge ert nen und...

Page 23: ...amenteelestadodelcabledealimentaci n Si stemanifiestaindicacionesdedesgastey oda os deber ser cambiado por el fabricante o por el servicio de asistencia t cnica del mismo ESPECIFICACIONES TECNICAS Ali...

Page 24: ...eyenda F1 Fusible 0 5 A r pido protecci n contra sobrecargas 24 Vac F2 Fusible 3 15 A r pido protecci n contra sobrecargas 230 Vac D1 Dip switch de selecci n funciones P1 Tecla de programaci n tiempos...

Page 25: ...n de los dispositivos de seguridad durante la fase de cierre realizar la inversi n de marcha 17 CSP_A entrada banda sensible anal gica 8 2 k 18 ANEM entrada sensor de viento v ase funcionamiento senso...

Page 26: ...ene la funci n de mando en secuencia Apertura Bloqueo Cierre Bloqueo Semi autom tico Dip 1 OFF Dip 2 ON cierre autom tico desactivado las teclas canal del emisor tienen la funci n A Apertura B Cierre...

Page 27: ...o contengan el c digo de dicha tecla se desactivar n con la emisi n de un bip de 5 segundos de duraci n sin embargo el que contenga el c digo emitir otro bip que durar un segundo entrando de hecho en...

Page 28: ...con las teclas 4 y 6 3 Pulsar la tecla 1 enviando de esta forma el control el LED L2 se iluminar de forma intermitente tres veces que se aliza que la anulaci n se ha cumplido con xito para anular otr...

Reviews: