Figure 13: Horizontal Vent Exhaust and Air Intake Configurations and Clearances
Figure 14: Horizontal Vent Exhaust and Air Intake Clearance
4. Vent outlet shall terminate at least 12” (0.30m) away from any forced air inlet. The combustion air intake should
never
terminate above the vent outlet.
5. If the vent exhaust and air intake are positioned on the same elevation, the minimum horizontal distance
between the two must be at the least, 24” (48” in colder climates).