1.0 GENERAL INFORMATION
1.1
INTRODUCTION
The Valiant FT
is a condensing, forced draft appliance
utilizing a premix power burner based on a push through
design which offers several venting options. Heat output is
controlled by the venturi and zero governor gas valve,
which work together to provide seamless modulation. It is
designed for use with a fully pumped and pressurized water
system. The turndown ratio for this appliance is up to 10:1
for natural gas models VA0110, VA0155, VA0199, VA0250,
VA0299 and VA0399 and 7:1 for VA0080. This results in
the appliance automatically modulating to provide heat
outputs from 100% down to approximately 10% of rated
input for models VA0110 to VA0399, and an appliance
output from 100% down to approximately 14% of rated input
for model VA0080. The turndown for propane units is 5:1
for all models.
1.2
CODES
The equipment shall be installed in accordance with those
installation regulations enforced in the local area where the
installation is to be made. In the absence of such
requirements, the installation shall conform to the latest
edition of the National Fuel Gas Code, ANSI Z223.1 and/or
CAN/CGAB149 Installation Code. All electrical wiring must
be done in accordance with the requirements of the
authority having jurisdiction or, in the absence of such
requirements, with National Electrical Code, ANSI/NFPA70
and/or the Canadian Electrical Code part 1 CSA C22.1.
Where required by the authority having jurisdiction, the
installation must conform to the American Society of
Mechanical Engineers Safety Code for Controls and Safety
Devices for Automatically Fired Boiler, ASME CSD-1. All
boilers conform to the latest edition of the ASME Boiler and
Pressure Vessel Code, Section II & IV. Where required by
the authority having jurisdiction, the installation must
comply with the CSA International, CAN/CGA-B149 and/or
local codes. This appliance meets the safe lighting
performance criteria with the gas manifold and control
assembly provided, as specified in the ANSI standards for
gas-fired units, ANSI Z21.13 & ANSI Z21.10
2.0 INSTALLATION
Upon receiving the unit, carefully check for
any signs of shipping damage. Pay particular attention
to parts accompanying the boiler, which may show
signs of being hit or otherwise being mishandled.
Verify total number of pieces shown on packing slip
with those actually received. In case there is damage or
a shortage, immediately notify carrier!
2.1
UNIT LOCATION
Install this appliance in a clean, dry location.
Site preparation for the Valiant FT should be carried out by
paying attention to the dimensions of the particular model
size and its overall clearances.
Figure 1: Wall-Hung Valiant FT
2.1.1 Overall Dimensions (Wall-Hung)
Model
Width
Depth
Height
080
19”
18 1/2”
37
110
19”
18 1/2”
37
155
19”
18 1/2”
37
199
21”
18 1/2”
38 5/16”
250
21”
18 1/2”
38 5/16”
299
23”
21”
40 5/16”
399
23”
21”
40 5/16”
Table 1: Wall-hung Valiant FT Overall Dimensions
The Valiant FT can also be easily converted into a floor
mounted unit with the addition of a floor stand kit. The water
and gas connections may need to be re-routed from the
bottom to the top for more convenience when installing the
Valiant FT as a floor mounted unit. The overall dimensions
of the floor mounted units are as below.
Summary of Contents for Valiant FT VA0080
Page 2: ......
Page 7: ......
Page 61: ...54 9 0 PIPING DIAGRAMS Figure 40 Single Boiler Hydronic Heating Zoned Piping...
Page 62: ...55 Figure 41 Multiple Boiler Hydronic Heating Zoned Piping...
Page 63: ...56 10 0 PARTS LIST...
Page 64: ...57...
Page 65: ...58...
Page 66: ...59...
Page 67: ...60...
Page 73: ...66 11 0 WIRING DIAGRAM...
Page 74: ...67 12 0 TUBING DIAGRAM...
Page 77: ...70...
Page 78: ...71 NOTES...
Page 79: ......