31
5.7
ERROR TABLE
There are three different type of error-groups:
Locking Errors
(Manually reset via the reset button)
Blocking Errors
(Automatically reset when the error is resolved)
Warnings
(will disappear when the warning is resolved; not stored in history)
5.7.1 Locking Errors (Manual Reset)
Table 26: Manual Reset Codes*
#
Error
Description
0 E2PROM_READ_ERROR
Internal software error
1 IGNIT_ERROR
Three unsuccessful ignition attempts in a row
2 GV_RELAY_ERROR
Failure detected in the GV relay
3 SAFETY_RELAY_ERROR
Failure detected in safety relay
4 BLOCKING_TOO_LONG
Control had a blocking error for more than 20 hours
5 FAN_ERROR_NOT_RUNNING
Fan is not running for more than 60 seconds
6 FAN_ERROR_TOO_SLOW
Fan runs too slow for more than 60 seconds
7 FAN_ERROR_TOO_FAST
Fan runs too fast for more than 60 seconds
8 RAM_ERROR
Internal software error
9 WRONG_EEPROM_SIGNATURE
Contents of E2prom is not up to date
10 E2PROM_ERROR
Wrong safety parameters in E2prom
11 STATE_ERROR
Internal software error
12 ROM_ERROR
Internal software error
13 APS_NOT_OPEN
Air pressure switch not opening during pre-purge 0
14 APS_NOT_CLOSED_IN_PRE_PURGE Air pressure switch not closing during pre-purge 1
15 MAX_TEMP_ERROR
The external overheat protection is enabled or the
Supply
sensor measures a
temp. of over
Prot_Overheat_Temp
-
SGOverheat_Duplex_Tolerance
for a
period of
Max_Value_Period
16 FLUE_GAS_ERROR
Flue temperature exceeded the maximum flue temperature
This error can only be reset when a jumper is placed on the board
17 STACK_ERROR
Internal software error
18 INSTRUCTION_ERROR
Internal software error
19 ION_CHECK_FAILED
Internal software error
20 FLAME_OUT_TOO_LATE
Flame still present 10 seconds after closing the gas valve
21 FLAME_BEFORE_IGNIT
Flame is detected before ignition
22 TOO_MANY_FLAME_LOSS
Three time flame lost during 1 demand
23 CORRUPTED_ERROR_NR
Error code RAM byte was corrupted to an unknown error code
24 FLUE_SWITCH_NOT_CLOSING
The blocked flue sensor is not closed within 10 minutes
25 TSUPPLY_DIFF_ERROR
The 2
Supply
sensors deviate too much for more than 60 seconds
26 TFLUE_DIFF_ERROR
The 2
Flue
sensors deviate too much for more than 60 seconds
27 FILLING_TOO_MUCH
Too many automated filling attempts in a short time period
28 FILL_TIME_ERROR
Filling takes too long
29 PSM_ERROR
Internal software error
30 REGISTER_ERROR
Internal software error
31 T_EXCHANGE_LOCK_ERROR
Exchange temperature exceeded the maximum temperature.
(only applicable to a 900PW control)
32 T_EXCHANGE_DIFF_ERROR
The 2 exchange sensors deviate too much for more than 60 seconds
33 LWCO_1_ERROR
Low water cut off 1 error
Summary of Contents for Valiant FT VA0080
Page 2: ......
Page 7: ......
Page 61: ...54 9 0 PIPING DIAGRAMS Figure 40 Single Boiler Hydronic Heating Zoned Piping...
Page 62: ...55 Figure 41 Multiple Boiler Hydronic Heating Zoned Piping...
Page 63: ...56 10 0 PARTS LIST...
Page 64: ...57...
Page 65: ...58...
Page 66: ...59...
Page 67: ...60...
Page 73: ...66 11 0 WIRING DIAGRAM...
Page 74: ...67 12 0 TUBING DIAGRAM...
Page 77: ...70...
Page 78: ...71 NOTES...
Page 79: ......