32
#
Error
Description
34 LWCO_2_ERROR
Low water cut off 2 error
35 APS_NOT_CLOSED_IN_POST_PURGE Air pressure switch not closing during post-purge 1
36 GAS_PRESSURE_ERROR
Gas pressure switch open for more than
E2_GPS_Timeout
37 AIR_DAMPER_LOCKING
More than 3 consecutive
Air_Damper_Error
have occurred
38 FLUE_PRESSURE_LOCKING
More than 3 flue pressure switch errors in 24 hrs
*
To eliminate the hard lockout error,
1) Press the on-board HMI touchscreen reset button to clear the error on screen.
2) Press the reset button on the 900PB operator display.
3) Press an externally connected reset button on a control input.
5.7.2 Blocking Errors (Automatic Reset)
Table 27: Automatic Reset Codes
#
Error
Description
100 WD_ERROR_RAM
Internal software error
101 WD_ERROR_ROM
Internal software error
102 WD_ERROR_STACK
Internal software error
103 WD_ERROR_REGISTER
Internal software error
104 WD_ERROR_XRL
Internal software error
105 HIGH_TEMP_ERROR
Supply
sensor measures over
Stay_Burning_Temp
for a period of
Max_Value_Period
106 REFHI_TOO_HIGH
Internal hardware error
107 REFHI_TOO_LOW
Internal hardware error
108 REFLO_TOO_HIGH
Internal hardware error
109 REFLO_TOO_LOW
Internal hardware error
110 REFHI2_TOO_HIGH
Internal hardware error
111 REFHI2_TOO_LOW
Internal hardware error
112 REFLO2_TOO_HIGH
Internal hardware error
113 REFLO2_TOO_LOW
Internal hardware error
114 FALSE_FLAME
Flame is detected in a state in which no flame is allowed to be seen
115 LOW_WATER_PRESSURE_ERROR Low water pressure error, generated when the water pressure switch opens
116 LOW_WATER_PRESSURE_SENSOR Low water pressure, generated when the water pressure drops below
Minimal_Pressure
, or when the water pressure drops below 0,3 bar
117 BLOCKED_DRAIN
Block drain switch is active
118 WD_COMM_ERROR
Watchdog communication error
119 RETURN_OPEN
Return sensor open
120 SUPPLY_OPEN
Supply sensor open
121 SUPPLY2_OPEN
Supply 2 sensor open
122 DHW_OPEN
DHW sensor open
123 FLUE_OPEN
Flue sensor open
124 FLUE2_OPEN
Flue 2 sensor open
125 OUTDOOR_OPEN
Outdoor sensor open
126 RETURN_SHORTED
Return sensor shorted
127 SUPPLY_SHORTED
Supply sensor shorted
128 SUPPLY2_SHORTED
Supply 2 sensor shorted
129 DHW_SHORTED
DHW sensor shorted
130 FLUE_SHORTED
Flue sensor shorted
Summary of Contents for Valiant FT VA0080
Page 2: ......
Page 7: ......
Page 61: ...54 9 0 PIPING DIAGRAMS Figure 40 Single Boiler Hydronic Heating Zoned Piping...
Page 62: ...55 Figure 41 Multiple Boiler Hydronic Heating Zoned Piping...
Page 63: ...56 10 0 PARTS LIST...
Page 64: ...57...
Page 65: ...58...
Page 66: ...59...
Page 67: ...60...
Page 73: ...66 11 0 WIRING DIAGRAM...
Page 74: ...67 12 0 TUBING DIAGRAM...
Page 77: ...70...
Page 78: ...71 NOTES...
Page 79: ......