30
Specific Parameters
Level
Default
Value
Range
Hx_Diff_DeltaT_Min
Minimum differential
over heat exchanger at
which burner load is
decreased.
3:Installer
10°C
50°F
-10 – 117°C
14 – 243°F
Hx_Diff_Max_Wait_Tim
e
Wait time after upper
limit primary heat
exchanger differential
has been exceeded.
3:Installer
5°C
41°F
-10 – 117°C
14 – 243°F
Table 25: Valiant FT Differential Temperature Settings for
Heat Exchanger
MODULE LOCKOUT FUNCTIONS
The Valiant FT control may lockout in either a manual reset condition requiring pushing the reset button to recycle the control
for a CSD1 requirement or an automatic reset condition. Pushing “RESET” with the control in a hard lockout condition is the
only way to reset the Valiant FT control. Turning the main power “OFF” and then “ON” or cycling the thermostat will not reset
a hard lockout condition. Wait until the display has synchronized before pushing “RESET” to clear a manual reset condition.
The Valiant FT control may proceed into a soft lockout condition. The boiler will stay in the automatic reset state until the fault
is corrected and will automatically return to normal operating state.
Summary of Contents for Valiant FT VA0080
Page 2: ......
Page 7: ......
Page 61: ...54 9 0 PIPING DIAGRAMS Figure 40 Single Boiler Hydronic Heating Zoned Piping...
Page 62: ...55 Figure 41 Multiple Boiler Hydronic Heating Zoned Piping...
Page 63: ...56 10 0 PARTS LIST...
Page 64: ...57...
Page 65: ...58...
Page 66: ...59...
Page 67: ...60...
Page 73: ...66 11 0 WIRING DIAGRAM...
Page 74: ...67 12 0 TUBING DIAGRAM...
Page 77: ...70...
Page 78: ...71 NOTES...
Page 79: ......