36
3.)
Power unit ON and set up addressing for the managing boiler.
4.)
Power unit(s) on and set up proper addressing for each member boiler.
6.2 Group: More than 16 units in Cascade
Cascading more than 16 units is an additional capability designated . This configuration requires the managing boiler
to parallelly cascade out from its “Cascade IN/OUT” terminal to up to 4 additional units. These 4 units can then be further
cascaded following section 6.1 to each have their own branch of cascaded boilers.
1.) Routing the correct communications wiring to each individual boiler.
On PB Menu; go to settings
Boiler settings
Enter installer password: 1100
Enter Module Cascade Settings
Burner Address set to “Managing”
Enter the total number of boilers in this
group including the managing boiler.
On PB Menu; go to settings
Boiler settings
Enter installer password: 1100
Enter Module Cascade Settings
Burner Address set to “Dependent X”
(each subsequent dependent boiler
should be addressed from 1 to 15)