Venting
The installation of venting must comply with national codes, local codes, and the
vent manufacturer’s instructions. Owner must refer to vent manufacturer’s
instructions and specifications. Z-Flex information can be found at
www.novaflex.com, please refer to page 48 for additional links.
The water heater must be vented to the outdoors as described in these
instructions. DO NOT connect this water heater to an existing Vent or Chimney, it
must be vented separately from all other appliances.
All vent components (adapters, pipe, elbows, terminals, etc.) should be UL 1738
Certified Stainless Steel Venting Material (e.g. AL29-4C).
The specified vent termination must be used. The termination should be a 90°
elbow type with screen. (Refer to page 48).
Use a vent pipe with an antidisconnection structure.
The use of a High Temperature Silicone (500’ F) may be required to seal vent
connections. To prevent accidental gas exhaust leakage, apply a 1/4” wide bead
approximately 1/4” from the end and another bead against the joint side of the
stop bead.
Follow vent manufacturer’s installation instructions.
The unit can be vented either horizontally or vertically.
Vent pipe runs must be adequately supported along both horizontal and vertical
runs.
The maximum recommended unsupported span should be no more than five (5)
feet. Support isolation hanging bands should be used. DO NOT use wire. (See
diagram below).
43
Visit Us: Camplux.com
3330-A Marathon Ct Charleston, SC 29418
1(844) 538-7475