D-48
Appendix D
Scanner
®
2000 microEFM
Units of Measurement
Value
Units
Scale
Offset
1502
A
0.0010000000
0.00
1601
cP
1.0000000000
0.00
1602
lbm/ft.sec
1488.1159420290
0.00
Log Capacity
Log Type
Capacity
Interval Logs (without expansion board)
2304
Interval Logs (with expansion board)
6392
Daily Logs
768
Event Logs
1152
Enron Log Data
The Scanner 2000 provides Enron Modbus® compliant downloads. For detailed instructions on downloading
interval, daily and event data, refer to
Specifications and Requirements for an Electronic Flow Measurement
Remote Terminal Unit for Enron Corp.
If an Enron host is not available or is too cumbersome or inefficient
for the host system, there are other methods that are available to retrieve the log data from the instrument.
Contact Cameron technical support for details.
The following registers are used for interval, daily and event log registers. Interval and daily records contain
16 user-configurable values. For details on the archive configuration, see Section 3 of the ModWorX Pro
Software User Manual. All of the Enron registers have an access type of Read Only (RO).
Enron Registers
Register
Description
Data Type
32
Enron Modbus® Event Log Register
Refer to Enron Event Record Format
700
Enron Modbus® Interval Log
Refer to Enron Interval/Daily Record Format
701
Enron Modbus® Daily Log
Refer to Enron Interval/Daily Record Format
7000
Interval Pointer
[1 to 2304, standard Scanner 2000]
[1 to 6392, Scanner 2000 plus
expansion board]
FP32
7001
Daily Pointer
[1 to 768]
FP32
7002
Event Counter
[1 to 2304]
FP32