E-6
Appendix E
Scanner
®
2000 microEFM
Table E.3—Analog Input Block Parameters
Index
Parameter
Definition
x13
IO_OPTS
Options for altering input and output block processing.
x14
STATUS_OPTS
Options which the user may select in the block processing of
status.
x15
CHANNEL
Identifies by number the logical hardware channel that is
connected to an AI block
x16
L_TYPE
Determines if the values passed by the transducer block to the
AI block may be used directly (Direct) or if the value is in different
units and must be converted linearly (Indirect), or with square root
(Ind Sqr Root), using the input range defined by the transducer
and the associated output range
x17
LOW_CUT
Limit used in square root processing. If the transducer value falls
below this limit, a value of zero percent of scale is used in block
processing.
x18
PV_FTIME
Time constant of a single exponential filter for the Primary value,
in seconds.
x19
FIELD_VAL
Raw value of the field device in percentage of the Primary value
range. Status reflects the Transducer condition before signal
characterization (L_TYPE) or filtering (PV_FTIME)."
x20
UPDATE_EVT
Alert generated by any change to the static data
x21
BLOCK_ALM
Alarm used for all configuration, hardware, connection failure or
system problems in the block. The cause of the alert is entered in
the subcode field.
x22
ALARM_SUM
Current alert status, unacknowledged states, unreported
states, and disabled states of the alarms associated with the
function block
x23
ACK_OPTION
Allows alarms associated with the block to be automatically
acknowledged
x24
ALARM_HYS
Amount the Primary value must return to within the alarm limits
before the alarm condition clears. Alarm hysteresis is expressed
as a percentage of the Primary value span.
x25
HI_HI_PRI
Priority of high high alarm
x26
HI_HI_LIM
Limit of high high alarm in engineering units
x27
HI_PRI
Priority of high alarm
x28
HI_LIM
Limit of high alarm in engineering units
x29
LO_PRI
Priority of low alarm
x30
LO_LIM
Limit of low alarm in engineering units
x31
LO_LO_PRI
Priority of low low alarm
x32
LO_LOLIM
Limit of low low alarm in engineering units
x33
HI_HI_ALM
Status for high high alarm and its associated time stamp
x34
HI_ALM
Status for high alarm and its associated time stamp
x35
LO_ALM
Status of the low alarm and its associated time stamp
x36
LO_LO_ALM
Status of the low low alarm and its associated time stamp
NOTE The maximum time required to execute a Scanner 2000 AI block is 30 ms.