C-9
Scanner
®
2000 microEFM
Appendix C
TO SCANNER 2000
MAIN BOARD,
TB1, TERMINALS 1-4
JUNCTION BOX
(OPTIONAL)
FROM RTD
(4-WIRE
RECOMMENDED)
Figure C.7—
F
oundation
™ fieldbus process temperature input wiring with junction box
Device Configuration
Basic parameters such as communications port slave address and baud rate, date and time, contract hour, and
plate size can be configured from the device keypad (
Configuration via Keypad, page 70
). All other parameters
must be configured using the ModWorX Pro software provided with the purchase of a Scanner 2000.
F
oundation
™ fieldbus configuration is performed with a customer-supplied configuration tool. For
basic instructions for configuring the function blocks that are integral to the Scanner 2000, see Fieldbus
Configuration below.
Fieldbus Configuration
At the core of the Scanner 2000 is an electronics package that measures and computes standard volumes of
gas, steam, petroleum liquids, and generic liquids with a high degree of accuracy and with very low power
consumption. These electronics communicate via RTU Modbus
®
.
The Scanner 2000 for
F
oundation
™ Fieldbus expands those capabilities to allow communication with
devices on a fieldbus network using
F
oundation
™ fieldbus H1 protocol. In addition to its native Modbus
®
communications, the Scanner 2000 publishes values for four process variables to a
F
oundation
™
fieldbus
network using an integrated fieldbus module.
The process variable values are written to a transducer block within the fieldbus module. When the process
variables are mapped to analog input blocks within the fieldbus module, those variable inputs are published to
the network and made available for development of process control strategies.