cable and  the motor cable of the fixed speed pump.

The connection with the power supply must
be 

made 

with 

interpositions 

of

magnetothermal  bipolar  switches  with
proper  size  and  with  a  type  A  differential
switch protected against untimely activation
and with threshold of intervention of  30 mA.

The use of the cascade mode with 1 fixed
speed  pump  not  allow  connection  of  a
remote  alarm  or  a  control  panel  remote
alarm RA100.

7.4.5. Cascade mode programming

Pressure  boosting  sets  with  2  variable  speed
pumps.

After the connection, change the AP09 parameter
from  OFF  to  UU  for  both  frequency  converters,
define  which  frequency  converter  will  work  on
master  mode  and  for  this  frequency  converter
change  the  AP10  parameter  from  SLA  (slave)  to
MAS (master).

Pressure  boosting  sets  with  3  variable  speed
pumps.

After the connection, change the AP09 parameter
from  OFF  to  UU  for  both  frequency  converters,
define  which  frequency  converter  will  work  on
master  mode  and  for  this  frequency  converter
change  the  AP10  parameter  from  SLA(slave)  to
MAS  (master).  Then  parameter  AP15  must  be
changed for each “slave” frequency converter. The
first  slave  frequency  converter  must  be  set  as
“SLA1”, and the second slave frequency converter
must be set as “SLA2”.
For  the  right  behavior  of  the  booster  set  it  is
recommended  to  switch  off  and  switch  on  all  the
frequency converter.

This configuration define an address for each
frequency converter, if not correctly configured,
cascade mode will not work properly.

Pressure  boosting  sets  with  1  variable  speed
pump and 1 fixed speed pump (single-phase).

After the connection, change the AP09 parameter
from OFF to UF for the frequency converter.

7.4.6. Cascade mode plant starting

Check that all the cascade mode parameters are
with  the  desired  values,  the  parameters  that  can
change the cascade mode operation are:

AP16

Cascade mode start fall pressure set-up

AP17

Cascade mode restart delay

AP18

Cascade mode fall pressure limit set-up

To  do  the  plant  starting  follow  the  instructions
under paragraph 12.

7.5. Float switch connection 

To  connect  a  float-switch  connect  to  the
connections 8-9  the cables of the float switch. The
float switch can be used for:

- dry-running protection

if,  in  cascade  mode,  the  frequency
converter  which  is  connected  the  float
switch  is  failure,  the  float  switch  cannot
shut off the pumps.

Electrical connection

7.6. Remote alarm connection

To  connect  a  remote  alarm  connect  to  the
connections  10-11  the  possible  remote  alarm  or
the control panel for remote alarm RA100.
The remote alarm can be used to signal:

- error  on  the  frequency  converter  (see

paragraph 9.3.) (nO).

- the frequency converter is running (nC).

Operating  limits:  250  Vac,  450  mA
maximum resistive current.

Electrical connection

4.93.413.3

+

-

4.93.413.7

+

RA 100

-

4.93.413.4

22

istr_P444_06_Easymat_ita_gb_F_E_D_r:istr_P444  29/08/14  15.49  Pagina 22

Summary of Contents for EASYMAT 5MM

Page 1: ...RUZIONI ORIGINALI PER L USO P 444 06 I Pagina 2 Italiano ORIGINAL OPERATING INSTRUCTIONS P 444 06 GB Page 16 English INSTRUCTIONS ORIGINALES POUR L UTILISATION P 444 06 F Page 30 Fran ais INSTRUCCIONE...

Page 2: ...on 8 Dry running protection 9 Parameters 9 1 Parameters of pump status 9 2 Programming parameters 10 Programming 10 1 PASSWORD Insertion 11 Parameters to check when starting up the unit 11 1 Vessel pr...

Page 3: ...quency of the pump being controlled Operating at a frequency higher than the allowable frequency can cause higher current absorption and damage to the device If it is necessary to remove the frequency...

Page 4: ...g protection tank fill float switch safety pressure switch Analogue inputs pressure transducer 4 20 mA Digital outputs general alarm the display shows the type of alarm see paragraphs 7 6 and 9 3 Conn...

Page 5: ...er 20s of system inactivity 5 3 3 Operating icons Constant pressure mode The system keeps the pressure constant when the quantity of water requested by the user changes Fixed speed mode The system wor...

Page 6: ...mum section of 2 5mm2 We also advise the use of insulated pin terminals Bad connections may damage the electronic circuit 7 1 Power supply line Power supply line must comply with the provisions under...

Page 7: ...g the instructions under paragraph 7 The power supply must comply the provisions of the paragraph 4 5 The connection with the power supply must be made with interpositions of magnetothermal bipolar sw...

Page 8: ...ecommended to switch off and switch on all the frequency converter This configuration define an address for each frequency converter if not correctly configured cascade mode will not work properly Pre...

Page 9: ...arameters are displayed Example 9 2 Programming parameters To display the programming parameters select menu Will be displayed progressively UP User settings these are the basis settings that user can...

Page 10: ...P04 Time before stop s 30 AP05 Dry run time s 10 AP06 First dry run time s 60 AP07 Dry run pressure bar 1 5 AP08 System dynamic 3 1 fast dynamic 5 slow dynamic AP09 Cascade mode oFF oFF UU cascade mod...

Page 11: ...fault Not connected cable broken connection pressure transducer spoiled Er03 Blockage due to low supply voltage Supply voltage lower than 190V The system automatically restart when the clamp voltage...

Page 12: ...nter the next number start blinking If the password is correct you can enter on the MENU if the password is wrong the first number restart blinking To exit the program push menu until you arrive on th...

Page 13: ...the pump by selecting stop as priming has not been carried out correctly and the pump is idling Re prime the pump and repeat the starting up procedure 12 1 Inversion of the direction of rotation To c...

Page 14: ...ction Converter failure 5 Watt flashing red light plus 75 dB 3600 Hz acoustic alarm for use in areas of loud noise positioned in such a way as to be visible from a distance The control panel is fitted...

Page 15: ...29 Modifica parametro Change parameter Changement de param tre Cambio de par metros Parameterwert ndern...

Page 16: ...4 1 4 93 414 2 4 93 414 3 Max 4 5 mm 90 20 Schemi collegamento elettrico Electrical connection scheme Sch mas du branchement lectrique Esquemas de conexi n el ctrica Schemata der elektrischen Anschl s...

Page 17: ...91 4 93 414 6 4 93 414 5 4 93 414 4...

Page 18: ...92 4 93 414 5 4 93 414 5 4 93 414 5...

Page 19: ...stallationsschema der Pumpe 22 1 Schemi installazione ad 1 pompa One pump installation scheme Sch mas de l installation 1 pompe Esquema de instalaci n a 1 bomba Installationsschema mit 1 Pumpe 1 21 Sc...

Page 20: ...22 2 Schemi installazione a 2 pompe Two pump installation scheme Sch mas de l installation 2 pompes Esquema de instalaci n a 2 bombas Installationsschema mit 2 Pumpen 2 4 93 412 4 94...

Page 21: ...tions des Directives 2004 108 CE 2006 95 CE et des normes harmonis es correspondantes CE EN 55014 1 CE EN 55022 CE EN 61000 3 3 CE EN 61000 4 2 CE EN 61000 4 3 CE EN 61000 4 4 CE EN 61000 4 5 CE EN 61...

Page 22: ...Montorso Vicentino Vicenza Italia Tel 39 0444 476476 Fax 39 0444 476477 E mail info calpeda it www calpeda it RoHS P 444 06 Con riserva di modifiche Changes reserved Modifications r serv es Con reser...

Reviews: