9.2.3. SA – Technical assistance settings

To enter password is required (see paragraph 10.1.)

Description

Standard Modifications Note

SA01
SA02
SA03

Pressure PID (Proportional gain)

2,8

SA04

Pressure PID (Integral time constant)

5,5

SA05

Pressure PID (Derivative time constant)

5,0

SA06

Min. run frequency

(Hz)

30

SA07

Max frequency

(Hz)

60

SA08

Set point pressure step up

(bar)

0,3

SA09

Pressure step up time

(s)

3

SA10

Pressure step up ramp

(bar/s)

0,3

SA11

Set point control ramp

(bar/s)

0,4

SA12

Carrier frequency

7010

SA13

Singlephase starting frequency

(Hz)

80

SA14  Singlephase starting voltage 

(V) 

195

SA15  Nominal voltage 

(V) 

220

9.2.4. MAn – Fixed speed mode activation

To enter password is required (see paragraph 10.1.)

Description

Standard Modifications Note

MAn1 Fixed speed mode activation

oFF

MAn2 Working frequency [MAn2 ≤ UP03]

(Hz)

45

a

9.3.  Alarms

Displayed alarm

Causes

Er01 Blockage due to no water

The device is in failure due to no water.
The system try to restart automatically.

- One attempt every 10 minutes for 6 times.
- One attempt every hour  for 24 times.
- One attempt every 24hours  for 30 times.

Er02 Pressure transducer fault

Not  connected  cable,  broken  connection,  pressure
transducer spoiled.

Er03 Blockage due to low supply voltage

Supply voltage lower than 190V.

- The system automatically restart when the clamp

voltage is higher than 190V.

Er04 Blockage due to high rectified voltage

Supply voltage higher than 250V.

- The system automatically restart when the clamp

voltage is lower than 250V.

Er05 Blockage for memory failure
Er06 Blockage due to overcurrent in the electro

pump motor

Er07 Blockage due to overcurrent in the 

frequency converter

Er08 Blockage due to direct short circuit between

the phases of output terminals

Er09 Blockage due to overheating
Er10 Blockage due to overheating of the power module
Er11 Blockage due to low voltage 24 V
Er12 Stop for float switch intervention

The system will restart with a delay defined by AP19
from the state variation of the float switch. The control
panel for remote alarm not report this alarm.

Er13 Internal hardware error

Contact the technical assistance

Er14 Cascade mode communication error

Check the RS 485 connection or that both pumps
are enabled.

In case of multiple fault, scroll with the buttons 

(plus) or 

(minus) to visualize the fault sequence.

In case of thermal block it is advised to check the causes that have created the problem before
restart the pump operation.

25

istr_P444_06_Easymat_ita_gb_F_E_D_r:istr_P444  29/08/14  15.49  Pagina 25

Summary of Contents for EASYMAT 5MM

Page 1: ...RUZIONI ORIGINALI PER L USO P 444 06 I Pagina 2 Italiano ORIGINAL OPERATING INSTRUCTIONS P 444 06 GB Page 16 English INSTRUCTIONS ORIGINALES POUR L UTILISATION P 444 06 F Page 30 Fran ais INSTRUCCIONE...

Page 2: ...on 8 Dry running protection 9 Parameters 9 1 Parameters of pump status 9 2 Programming parameters 10 Programming 10 1 PASSWORD Insertion 11 Parameters to check when starting up the unit 11 1 Vessel pr...

Page 3: ...quency of the pump being controlled Operating at a frequency higher than the allowable frequency can cause higher current absorption and damage to the device If it is necessary to remove the frequency...

Page 4: ...g protection tank fill float switch safety pressure switch Analogue inputs pressure transducer 4 20 mA Digital outputs general alarm the display shows the type of alarm see paragraphs 7 6 and 9 3 Conn...

Page 5: ...er 20s of system inactivity 5 3 3 Operating icons Constant pressure mode The system keeps the pressure constant when the quantity of water requested by the user changes Fixed speed mode The system wor...

Page 6: ...mum section of 2 5mm2 We also advise the use of insulated pin terminals Bad connections may damage the electronic circuit 7 1 Power supply line Power supply line must comply with the provisions under...

Page 7: ...g the instructions under paragraph 7 The power supply must comply the provisions of the paragraph 4 5 The connection with the power supply must be made with interpositions of magnetothermal bipolar sw...

Page 8: ...ecommended to switch off and switch on all the frequency converter This configuration define an address for each frequency converter if not correctly configured cascade mode will not work properly Pre...

Page 9: ...arameters are displayed Example 9 2 Programming parameters To display the programming parameters select menu Will be displayed progressively UP User settings these are the basis settings that user can...

Page 10: ...P04 Time before stop s 30 AP05 Dry run time s 10 AP06 First dry run time s 60 AP07 Dry run pressure bar 1 5 AP08 System dynamic 3 1 fast dynamic 5 slow dynamic AP09 Cascade mode oFF oFF UU cascade mod...

Page 11: ...fault Not connected cable broken connection pressure transducer spoiled Er03 Blockage due to low supply voltage Supply voltage lower than 190V The system automatically restart when the clamp voltage...

Page 12: ...nter the next number start blinking If the password is correct you can enter on the MENU if the password is wrong the first number restart blinking To exit the program push menu until you arrive on th...

Page 13: ...the pump by selecting stop as priming has not been carried out correctly and the pump is idling Re prime the pump and repeat the starting up procedure 12 1 Inversion of the direction of rotation To c...

Page 14: ...ction Converter failure 5 Watt flashing red light plus 75 dB 3600 Hz acoustic alarm for use in areas of loud noise positioned in such a way as to be visible from a distance The control panel is fitted...

Page 15: ...29 Modifica parametro Change parameter Changement de param tre Cambio de par metros Parameterwert ndern...

Page 16: ...4 1 4 93 414 2 4 93 414 3 Max 4 5 mm 90 20 Schemi collegamento elettrico Electrical connection scheme Sch mas du branchement lectrique Esquemas de conexi n el ctrica Schemata der elektrischen Anschl s...

Page 17: ...91 4 93 414 6 4 93 414 5 4 93 414 4...

Page 18: ...92 4 93 414 5 4 93 414 5 4 93 414 5...

Page 19: ...stallationsschema der Pumpe 22 1 Schemi installazione ad 1 pompa One pump installation scheme Sch mas de l installation 1 pompe Esquema de instalaci n a 1 bomba Installationsschema mit 1 Pumpe 1 21 Sc...

Page 20: ...22 2 Schemi installazione a 2 pompe Two pump installation scheme Sch mas de l installation 2 pompes Esquema de instalaci n a 2 bombas Installationsschema mit 2 Pumpen 2 4 93 412 4 94...

Page 21: ...tions des Directives 2004 108 CE 2006 95 CE et des normes harmonis es correspondantes CE EN 55014 1 CE EN 55022 CE EN 61000 3 3 CE EN 61000 4 2 CE EN 61000 4 3 CE EN 61000 4 4 CE EN 61000 4 5 CE EN 61...

Page 22: ...Montorso Vicentino Vicenza Italia Tel 39 0444 476476 Fax 39 0444 476477 E mail info calpeda it www calpeda it RoHS P 444 06 Con riserva di modifiche Changes reserved Modifications r serv es Con reser...

Reviews: