23

8. Dry-running protection

The  frequency  converter  is  equipped  with  a  dry-
running  protection  for  the  pumps.  When  the
pressure  on  the  system  remain  for  a  time  higher
than  the  dry-run  time  (AP05)  lower  than  value  of
the dry-run pressure (AP07) the protection system
stop the pump. It is possible the use of an external
float  switch  for  the  dry-running  protection  (see
paragraph 7.5.). In this case the pumps start with
a delay time (in seconds) defined by AP19 (Digital
input  restart  time),  the  time  will  be  counted  after
the change of the float switch state. 
For  entering  the  programming  mode  see
paragraph 10.

9. Parameters

On  the  frequency  converter  the  following
informations are displayed:
- Parameters of pump status.
- Programming parameters.
- Alarms.

9.1. Parameters of pump status

They allow to visualize:
- the  modulation  frequency  of  the  pump  (basic

display).

- the pressure of the system.
- the line absorbed current.

Starting  form  the  basic  display  by  pushing  of  the

directional  arrow 

(plus)  or 

(minus)  the

other parameters are displayed.
Example:

9.2. Programming parameters

To  display  the  programming  parameters,  select

(menu).

Will be displayed progressively:

UP - User  settings:

these  are  the  basis  settings

that user can change.

AP - Advanced  settings:

these  settings  are

available only to qualified personnel. To enter
password is required (see paragraph 10.1.).

SA - Technical  assistance  settings:

these  are

the  advanced  parameters,  only  technical
assistance  personnel  are  allowed  to  access
this  menu.  Password  is  required  (see
paragraph 10.1.).

MAn - Fixed speed mode activation:

this allows

activation of the fixed speed mode and the
working 

frequency. 

Only 

qualified

personnel are allowed to access this menu.
Password  is  required  (see  paragraph
10.1.).

AE - Advanced  parameters:

this  allows  for  the

display  of  secondary  parameters  which  can
be useful for system diagnostics.

AE01

Software release

AE02

Supply voltage

(V)

AE03

Last 5 faults

Supply voltage visualization example.

By  pushing  the 

button  (menu)  the  UP

parameter  appears.  Select  the  AE  parameter  by

pushing  the 

(plus)  up  to  arrive  at  the  correct

parameter 

,  confirm  with 

(enter).

Select  the  parameter 

by  pushing  the

button 

(plus)  and  confirm  with 

(enter).

Supply voltage is displayed.

istr_P444_06_Easymat_ita_gb_F_E_D_r:istr_P444  29/08/14  15.49  Pagina 23

Summary of Contents for EASYMAT 5MM

Page 1: ...RUZIONI ORIGINALI PER L USO P 444 06 I Pagina 2 Italiano ORIGINAL OPERATING INSTRUCTIONS P 444 06 GB Page 16 English INSTRUCTIONS ORIGINALES POUR L UTILISATION P 444 06 F Page 30 Fran ais INSTRUCCIONE...

Page 2: ...on 8 Dry running protection 9 Parameters 9 1 Parameters of pump status 9 2 Programming parameters 10 Programming 10 1 PASSWORD Insertion 11 Parameters to check when starting up the unit 11 1 Vessel pr...

Page 3: ...quency of the pump being controlled Operating at a frequency higher than the allowable frequency can cause higher current absorption and damage to the device If it is necessary to remove the frequency...

Page 4: ...g protection tank fill float switch safety pressure switch Analogue inputs pressure transducer 4 20 mA Digital outputs general alarm the display shows the type of alarm see paragraphs 7 6 and 9 3 Conn...

Page 5: ...er 20s of system inactivity 5 3 3 Operating icons Constant pressure mode The system keeps the pressure constant when the quantity of water requested by the user changes Fixed speed mode The system wor...

Page 6: ...mum section of 2 5mm2 We also advise the use of insulated pin terminals Bad connections may damage the electronic circuit 7 1 Power supply line Power supply line must comply with the provisions under...

Page 7: ...g the instructions under paragraph 7 The power supply must comply the provisions of the paragraph 4 5 The connection with the power supply must be made with interpositions of magnetothermal bipolar sw...

Page 8: ...ecommended to switch off and switch on all the frequency converter This configuration define an address for each frequency converter if not correctly configured cascade mode will not work properly Pre...

Page 9: ...arameters are displayed Example 9 2 Programming parameters To display the programming parameters select menu Will be displayed progressively UP User settings these are the basis settings that user can...

Page 10: ...P04 Time before stop s 30 AP05 Dry run time s 10 AP06 First dry run time s 60 AP07 Dry run pressure bar 1 5 AP08 System dynamic 3 1 fast dynamic 5 slow dynamic AP09 Cascade mode oFF oFF UU cascade mod...

Page 11: ...fault Not connected cable broken connection pressure transducer spoiled Er03 Blockage due to low supply voltage Supply voltage lower than 190V The system automatically restart when the clamp voltage...

Page 12: ...nter the next number start blinking If the password is correct you can enter on the MENU if the password is wrong the first number restart blinking To exit the program push menu until you arrive on th...

Page 13: ...the pump by selecting stop as priming has not been carried out correctly and the pump is idling Re prime the pump and repeat the starting up procedure 12 1 Inversion of the direction of rotation To c...

Page 14: ...ction Converter failure 5 Watt flashing red light plus 75 dB 3600 Hz acoustic alarm for use in areas of loud noise positioned in such a way as to be visible from a distance The control panel is fitted...

Page 15: ...29 Modifica parametro Change parameter Changement de param tre Cambio de par metros Parameterwert ndern...

Page 16: ...4 1 4 93 414 2 4 93 414 3 Max 4 5 mm 90 20 Schemi collegamento elettrico Electrical connection scheme Sch mas du branchement lectrique Esquemas de conexi n el ctrica Schemata der elektrischen Anschl s...

Page 17: ...91 4 93 414 6 4 93 414 5 4 93 414 4...

Page 18: ...92 4 93 414 5 4 93 414 5 4 93 414 5...

Page 19: ...stallationsschema der Pumpe 22 1 Schemi installazione ad 1 pompa One pump installation scheme Sch mas de l installation 1 pompe Esquema de instalaci n a 1 bomba Installationsschema mit 1 Pumpe 1 21 Sc...

Page 20: ...22 2 Schemi installazione a 2 pompe Two pump installation scheme Sch mas de l installation 2 pompes Esquema de instalaci n a 2 bombas Installationsschema mit 2 Pumpen 2 4 93 412 4 94...

Page 21: ...tions des Directives 2004 108 CE 2006 95 CE et des normes harmonis es correspondantes CE EN 55014 1 CE EN 55022 CE EN 61000 3 3 CE EN 61000 4 2 CE EN 61000 4 3 CE EN 61000 4 4 CE EN 61000 4 5 CE EN 61...

Page 22: ...Montorso Vicentino Vicenza Italia Tel 39 0444 476476 Fax 39 0444 476477 E mail info calpeda it www calpeda it RoHS P 444 06 Con riserva di modifiche Changes reserved Modifications r serv es Con reser...

Reviews: