9.2.1. UP – User settings
N°
Description
Standard Modifications Note
UP01
restart mode power failure
rA
[rA = automatic; rM = manual]
UP02
Nominal pump current
(A)
0,1
UP03
Nominal pump frequency
(Hz)
50
UP04
Direction of rotation
---
[ --- = std rotation; --- = inverted rotation]
UP05
Set point pressure
(bar)
1,5
9.2.2. AP – Advanced settings
To enter password is required (see paragraph 10.1.)
N°
Description
Standard Modifications Note
AP01
Pressure transducer set-up
(bar)
10
[sensor full-scale]
AP02
Ramp down
(s)
3
AP03
Ramp-up
(s)
2 MT
(fixed value for MM)
0 MM
AP04
Time before stop
(s)
30
AP05
Dry-run time
(s)
10
AP06
First dry-run time
(s)
60
AP07
Dry-run pressure
(bar)
1,5
AP08
System dynamic
3
[1 = fast dynamic; 5 = slow dynamic]
AP09
Cascade mode
oFF
[oFF; UU = cascade mode with double inverter;
UF = cascade mode with an inverter]
AP10
Master/Slave setting
SLA
MAS = master; SLA = slave
AP11
Reset to factory set-up
AP12
Digital input activation
1
[0 = oFF; 1 = no; 2 = nC]
AP13
Digital output activation
0
[0 = oFF; 1 = on; 2 = no; 3 = nC]
AP14
Restart fall pressure set-up
(bar)
AP15
Pump address
SLA1
AP16
Cascade mode start fall pressure set-up (bar)
0,3
AP17
Cascade mode restart delay
(s)
10
AP18
Cascade mode fall pressure limit set-up (bar)
0,6
AP19
Digital input delay time
(s)
30
[float switch delay time]
24
4.93.410
P460