10. Programming

To  enter  programming,  select 

(menu).  Use

the buttons 

(plus) or 

(minus) to move to the

programming parameter to be modified and select

(enter) to confirm. Use the buttons 

(plus)

or 

(minus)  to  move  to  the  parameter  to  be

modified  and  select 

(enter)  to  confirm,  with

the  buttons 

(plus)  or 

(minus)  increase  or

decrease the value. From this moment the set-up

icon 

start blinking until the value is confirmed

with 

(enter).

To exit the program, push 

(menu) until when

you arrive on the basic display.
When you go in the set-up mode appear the icon

.

Example of parameter variation.

In order to modify the set point pressure from 3.0
bars to a 2.8 bars:

select 

(menu) and then with the buttons 

(plus)  or 

(minus)  until  you  move  to

programming  parameter  UP.  Confirm  with

(enter) and then with the buttons 

(plus) or 

(minus)  move  to  the  parameter  UP05.  Confirm

with 

(enter)  and  then  with  the  buttons 

(plus)  or 

(minus)  change  the  value  up  to  the

desired  value.  From  this  moment  the  set-up  icon

start blinking  until the value is confirmed with

(enter).

To  exit  the  program,  push 

(menu)  until  you

arrive on the basic video, when you are out from

the set-up mode the icon disappear 

.

10.1. PASSWORD insertion

To enter on a menu with password, four numbers
appear  on  the  display,  the  number  to  insert  is

blinking.  By  pushing    buttons 

(plus)  or

(minus) you can change the blinking value. If you

confirm  with 

(enter)  the  next  number  start

blinking.
If  the  password  is  correct  you  can  enter  on  the
MENU, if the password is wrong the first number
restart blinking.

To  exit  the  program,  push 

(menu)  until  you

arrive on the basic display, when you are out from

the set-up mode the icon disappear 

.

password

value

user

1959

Technical assistance

contact  the  technical
assistance

11. Parameters  to  check  when

starting up the unit

There  are  4  programming  parameters  that  need
to be checked when the unit is started up:

• Parameter UP02 NOMINAL PUMP CURRENT

The nominal current of the pump must be set.

If the value input is inappropriate there is
the  risk  of  pump  damage  or  to  have  an
unexpected overcurrent alarm.

• Parameter 

UP03 

NOMINAL 

PUMP

FREQUENCY

The nominal frequency of the pump must be set. 

If the value input is inappropriate there is
the  risk  of    higher  current  absorption  or
pump damage.

• Parameter UP05 SET POINT PRESSURE

The working pressure of the pump must be set. 

If  the  value  input  is  inappropriate  for  the  needs
of  the  system,  the  value  can  be  increased  or

decreased  using  the 

(plus)  or 

(minus)

keys.

If during the first start-up of the unit, filling
the system takes longer than 1 minute and
the  unit  signals  a    dry-running  alarm,
Increase  the  parameter  AP06,  until  the
pressure rises above the set value and the
pump  remain  on.  (Make  sure  the  pump
are primed).

11.1. Vessel pressure

Once the new working pressure is entered,
the  tank  pre-loaded  pressure  must  be
changed to be 2/3 of the working pressure
(i.e.  4  bar  working  pressure,tanks  to  be
pre-loaded at 2.7 bar).

26

istr_P444_06_Easymat_ita_gb_F_E_D_r:istr_P444  29/08/14  15.49  Pagina 26

Summary of Contents for EASYMAT 5MM

Page 1: ...RUZIONI ORIGINALI PER L USO P 444 06 I Pagina 2 Italiano ORIGINAL OPERATING INSTRUCTIONS P 444 06 GB Page 16 English INSTRUCTIONS ORIGINALES POUR L UTILISATION P 444 06 F Page 30 Fran ais INSTRUCCIONE...

Page 2: ...on 8 Dry running protection 9 Parameters 9 1 Parameters of pump status 9 2 Programming parameters 10 Programming 10 1 PASSWORD Insertion 11 Parameters to check when starting up the unit 11 1 Vessel pr...

Page 3: ...quency of the pump being controlled Operating at a frequency higher than the allowable frequency can cause higher current absorption and damage to the device If it is necessary to remove the frequency...

Page 4: ...g protection tank fill float switch safety pressure switch Analogue inputs pressure transducer 4 20 mA Digital outputs general alarm the display shows the type of alarm see paragraphs 7 6 and 9 3 Conn...

Page 5: ...er 20s of system inactivity 5 3 3 Operating icons Constant pressure mode The system keeps the pressure constant when the quantity of water requested by the user changes Fixed speed mode The system wor...

Page 6: ...mum section of 2 5mm2 We also advise the use of insulated pin terminals Bad connections may damage the electronic circuit 7 1 Power supply line Power supply line must comply with the provisions under...

Page 7: ...g the instructions under paragraph 7 The power supply must comply the provisions of the paragraph 4 5 The connection with the power supply must be made with interpositions of magnetothermal bipolar sw...

Page 8: ...ecommended to switch off and switch on all the frequency converter This configuration define an address for each frequency converter if not correctly configured cascade mode will not work properly Pre...

Page 9: ...arameters are displayed Example 9 2 Programming parameters To display the programming parameters select menu Will be displayed progressively UP User settings these are the basis settings that user can...

Page 10: ...P04 Time before stop s 30 AP05 Dry run time s 10 AP06 First dry run time s 60 AP07 Dry run pressure bar 1 5 AP08 System dynamic 3 1 fast dynamic 5 slow dynamic AP09 Cascade mode oFF oFF UU cascade mod...

Page 11: ...fault Not connected cable broken connection pressure transducer spoiled Er03 Blockage due to low supply voltage Supply voltage lower than 190V The system automatically restart when the clamp voltage...

Page 12: ...nter the next number start blinking If the password is correct you can enter on the MENU if the password is wrong the first number restart blinking To exit the program push menu until you arrive on th...

Page 13: ...the pump by selecting stop as priming has not been carried out correctly and the pump is idling Re prime the pump and repeat the starting up procedure 12 1 Inversion of the direction of rotation To c...

Page 14: ...ction Converter failure 5 Watt flashing red light plus 75 dB 3600 Hz acoustic alarm for use in areas of loud noise positioned in such a way as to be visible from a distance The control panel is fitted...

Page 15: ...29 Modifica parametro Change parameter Changement de param tre Cambio de par metros Parameterwert ndern...

Page 16: ...4 1 4 93 414 2 4 93 414 3 Max 4 5 mm 90 20 Schemi collegamento elettrico Electrical connection scheme Sch mas du branchement lectrique Esquemas de conexi n el ctrica Schemata der elektrischen Anschl s...

Page 17: ...91 4 93 414 6 4 93 414 5 4 93 414 4...

Page 18: ...92 4 93 414 5 4 93 414 5 4 93 414 5...

Page 19: ...stallationsschema der Pumpe 22 1 Schemi installazione ad 1 pompa One pump installation scheme Sch mas de l installation 1 pompe Esquema de instalaci n a 1 bomba Installationsschema mit 1 Pumpe 1 21 Sc...

Page 20: ...22 2 Schemi installazione a 2 pompe Two pump installation scheme Sch mas de l installation 2 pompes Esquema de instalaci n a 2 bombas Installationsschema mit 2 Pumpen 2 4 93 412 4 94...

Page 21: ...tions des Directives 2004 108 CE 2006 95 CE et des normes harmonis es correspondantes CE EN 55014 1 CE EN 55022 CE EN 61000 3 3 CE EN 61000 4 2 CE EN 61000 4 3 CE EN 61000 4 4 CE EN 61000 4 5 CE EN 61...

Page 22: ...Montorso Vicentino Vicenza Italia Tel 39 0444 476476 Fax 39 0444 476477 E mail info calpeda it www calpeda it RoHS P 444 06 Con riserva di modifiche Changes reserved Modifications r serv es Con reser...

Reviews: