background image

GB

CT,T, TP,  Rev22 - Operating Instructions

Page 

5

prevent foreign particles from entering the pump.

6.4.3. Delivery pipe

Fit a gate valve in the delivery pipe to adjust delivery 

and head.

Install a pressure gauge.

With a geodetic head at outlet over 15 m fit a check 

valve between the pump and the gate valve in order to 

protect the pump from water hammering.

6.5. Electrical connection

OFF

  Electrical connection must be carried out only 

by  a  qualified  electrician  in  accordance  with 

local regulations.

Follow all safety standards.

The unit must be properly earthed (grounded).

Connect the earthing (grounding) conductor to the 

terminal with the   marking. 

Compare the frequency and mains voltage with the 

name-plate data and connect the supply conductors 

to the terminals in accordance with the appropriate 

diagram inside the terminal box cover.

  ATTENTION: never allow washers or other 

metal parts to fall into the internal cable 

opening between the terminal box and 

stator. If this occurs, dismantle the motor to 

recover the object which has fallen inside.

 ATTENTION: with motor power rating ≥ 5.5 kW 

avoid direct starting. Provide a control panel 

with star-delta starting or an  other starting 

device.

If the terminal box is provided with an inlet gland, use 

a flexible power supply cord of the H07 RN-F type with 

section of cable  not less than 11 TAB IEC 60335-1.

If the terminal box is provided with an inlet bushing, 

connect the power supply cord through a conduit.

For use in swimming pools (not when persons are in 

the pool), garden ponds and similar places, a residual 

current device with IΔN not exceeding 30 mA must be 

installed in the supply circuit.

Install a device for disconnection from the mains 

(switch) with a contact separation of at least 3 mm in 

all poles.

With a three-phase motor install an overload protection 

device with curve D appropriate for the rated current 

of the pump.

Single-phase  CTM, TM, TPM, are supplied with a 

capacitor connected to the terminals and (for 220-240 

V - 50 Hz) with an incorporated thermal protector.

7. STARTUP AND OPERATION
7.1.  Preliminary checks before start-up of the

pump

Do not start-up the device in case of damaged parts.

7.2. First starting

OFF

ATTENTION: never run the pump dry. Start the 

pump after filling it completely with liquid.

When the pump is located above the water level 

(suction lift operation) or with a positive suction head 

which is too low (less than 1 m) to open the non-return 

valve, fill the pump through the priming hole.

When the liquid level on the suction side is above 

the pump (inflow under positive  suction head), fill the 

pump by opening the suction gate valve slowly and 

completely, keeping the delivery gate valve open to 

release the air.

Before starting, check that the shaft turns by hand. For 

this purpose use the screwdriver notch on the shaft 

end on the ventilation side.

  Slight initial rotational resistance may be due to 

the reduced axial clearance of the impeller of 

this type of pump; the impeller will work loose 

after a short period of use.

When starting, with a three-phase motor, check 

that the direction of rotation is as shown by the 

arrows on the lantern bracket. 

Otherwise, disconnect electrical power and reverse 

the connections of two phases.

Check that the pump works within its 

field  of  perfor-mance  and  that  the  absorbed  current 

shown on the name-plate is not exceeded. Otherwise 

adjust the delivery gate valve or the setting of any 

pressure switches.

These pumps must never be run against a closed 

valve.

  Never  run  the  pump  for  more  than  five 

minutes with a closed gate valve.

7.3. Switch off of the pump

ON

  The appliance must be switch off every time 

there are faults. (see troubleshooting).

The product is designed for a continuous duty,  the 

switch off is performed by disconnecting the power 

supply by means the expected disconnecting devices. 

(see paragraph “6.5 Electrical connection”).

8. MAINTENANCE

Before any operations it's necessary to disconnect the

power supply. 

If required ask to an electrician or to an expert

technician.

  Every maintenance operations, cleaning or 

reparation executed with the electrical system 

under voltage, it could cause serious injuries 

to people.

In case of extraordinary maintenance, or maintenance 

operations that require part-removing, the operator 

must be a qualified technician able to read schemes 

and drawings.

It is suggest to  register all maintenance operation 

executed. 

i

  During maintenance keep particular attention in 

order to avoid the introduction of small external 

parts, that could compromise the device safety.

Summary of Contents for CT Series

Page 1: ...Page English P gina Espa ol...

Page 2: ...d section of the power cable chapter 6 5 The type of electrical protection to be installed chapter 6 5 1 1 Symbols To improve the understanding of the manual below are indicated the symbols used with...

Page 3: ...e of the device is forbidden as is use under conditions other than those indicated in these instructions Improper use of the product reduces the safety and the efficiency of the device Calpeda shall n...

Page 4: ...e technical catalogue 6 2 Ambient requirements and installation site dimensions The customer has to prepare the installation site in order to guarantee the right installation and in order to fulfill t...

Page 5: ...st starting OFF ATTENTION never run the pump dry Start the pump after filling it completely with liquid When the pump is located above the water level suction lift operation or with a positive suction...

Page 6: ...ves before dismantling For dismantling and re assembly see construction in the cross section drawing To remove the impeller 28 00 T TP use the threaded dismantling holes 9 DISPOSAL OFF The final dispo...

Page 7: ...ary replace it See point 2a also 4 Insufficient flow 4a Pipes and accessories with diameter too small causing excessive loss of head 4b Presence of deposits or solid bodies in the internal passages of...

Page 8: ...que se instalar el Cap tulo 6 5 1 1 S mbolos utilizados Para mejorar la comprensi n se utilizan los s mbolos pictogramas a continuaci n con sus significados Informaci n y advertencias que deben respet...

Page 9: ...ise ado y fabricado exclusivamente para el uso descrito en el p r 2 1 Est totalmente prohibida la utilizaci n del dispositivo para usos impropios y que no est n indicados en este manual El uso impropi...

Page 10: ...e ser golpeado Hay que evitar la superposici n al embalado de otro material que podr a da ar la bomba Si el peso supera los 25 Kg el embalado tiene que ser levantado por dos personas al mismo tiempo 6...

Page 11: ...s y para 220 240 50Hz con termoprotector incorporado 7 ARRANQUE Y USO 7 1 Controles antes del arranque La bomba no debe funcionar en presencia de parte deteriorada 7 2 Primer arranque OFF ATENCI N Evi...

Page 12: ...r que el rodete no esta bloqueado por incrustaciones o por otras causas Limpiar eventualmente con adecuada precauci n 8 2 Desmontaje del sistema Antes del desmontaje cierre las compuertas en aspiraci...

Page 13: ...aci n c Limpiar el filtro si es necesario sustituirlo Ver tambi n el punto 2a 4 Caudal insuficiente a Tuber a y accesorios con di metro demasiado peque o que provocan excesivas perdidas de carga b Pre...

Page 14: ...g and assembly Dibujo para desmontaje y montaje 98 04 46 00 28 00 76 00 14 00 14 04 28 20 76 04 94 00 76 54 98 00 82 00 88 00 82 04 82 08 81 00 81 08 78 00 73 12 73 00 36 00 14 20 36 52 36 50 90 00 14...

Page 15: ...00 92 00 46 00 70 18 36 50 14 12 12 20 81 00 82 04 94 02 76 04 94 00 76 54 98 00 98 08 14 00 98 04 70 00 14 04 82 00 90 00 88 00 3 94 112 28 20 28 00 12 00 14 20 3 94 114 14 00 14 24 14 24 32 00 14 1...

Page 16: ...40 2009 DECLARACION DE CONFORMIDAD En CALPEDA S p A declaramos bajo nuestra exclusiva responsabilidad que las Bombas CT T TP B I M modelo y numero de serie marcados en la placa de caracteristicas son...

Reviews: