Exit Loops
28
Figure A
If you purchased a Calimet Loop Detector Plugin, see the wiring diagram below to connect
the loop detector to the gate operator circuit board. The loop lead-in wires will connect
directly on the loop detector.
For other brand exit loops or exit wands, use the Exit Loop relay, and the 24-VDC and 24V-
COM if using the gate operator to power the device.
For reverse loops located on the inside of the gate, use the PHANTOM relay. For reverse
loops located on the outside of the gate, use the SAFETY relay.
The exit loop relays are located on the bottom right of the gate operator circuit board.
Loop to Gate Operator Wiring Diagram
• Reverse Loop (outside)
→
SAFETY
• Reverse Loop (Phantom) (inside)
→
PHANTOM
• Exit Loop
→
EXIT LOOP
LOOPDETECTOR
CL
PED-SW
SAFETY
PHANTOM
EXIT LOOP
24-VDC
24V-COM
Loop wire
3 Turns
Sealant
Above Ground
Backer Rod
Loop Size
(Sq ft)
Number
of Turns
6' to 12'
6
61' to 240'
3
2
5
21' to 60'
4
0.2"
241'+
13' to 20'
1.5"