SATK20 & SATK30

2

General Information

Please leave the manual as a reference guide for the user. 

Dispose of any packaging in an appropriate manner, most 
of which can be recycled.

In this Installation, Operation and Maintenance guide we 
have endeavoured to make the information as accurate as 
possible.

We cannot accept any responsibility should it be found 
that in any respect the information is inaccurate or 
incomplete or becomes so as a result of further 
developments or changes to the products. 

Key to Symbols

Safety Instructions

6

Water temperatures higher than 50˚C may cause severe 
burns. When installing, commissioning and maintaining the 
device, take the necessary precautions so that these 
temperatures will not be hazardous for people.

7

In the case of particularly hard or impure water, there must 
be suitable provision for filtering and treating the water 
before it enters the device, in accordance with current 
legislation. Failure to do so may result the HIU becoming 
damaged or working incorrectly.

8

Any use of the HIU other than it’s intended use is prohibited.

9

Any coupling of the device with other system components 
must be made while taking the operational characteristics of
both units into consideration.

10

An incorrect coupling could compromise the operation of 
the device and/or system.

NOTE: Risk of electric shock. Live parts. Shut off the electric 

supply before opening the HIU cover.

1

During installation and maintenance operations, always 
avoid direct contact with live or potentially hazardous parts.

2

The device must not be exposed to water drops or humidity, 
direct sunlight, the elements, heat sources or high intensity 
electromagnetic fields.

This device cannot be used in areas at risk of explosion or 
fire.

3

The device must be connected to an independent bipolar 
switch. If work has to be done on the device, switch off the 
electric supply first. Do not use devices with automatic or 
time reset, or which may be reset accidentally.

4

Use suitable automatic protection devices in compliance 
with current legislation.

5

The device must always be earthed before it is connected to 
the electric supply. If the device has to be removed, always 
disconnect the earth connection after disconnecting the 
electric supply. Check that the earth connection has been 
made to the highest of standards under current legislation.

6

Electrical installation must only be carried out by a qualified 
technician, in accordance with current requirements.

Primary circuit flow

Primary circuit return

Domestic hot water outlet

Domestic cold water inlet

Low temperature circuit flow

Low temperature circuit return

Medium temperature circuit flow

Medium temperature circuit return

High temperature circuit flow

High temperature circuit return

Summary of Contents for Altecnic SATK20

Page 1: ...SATK20 SATK30 heat interface unit Installation Operation Maintenance Instructions...

Page 2: ...roduct range 1 Safety instructions 1 Dimensions and technical speci cation 3 Installation 4 First operation 5 Electronic controller 6 Safety and alarms 7 SATK20103 and SATK20203 components 8 SATK20303...

Page 3: ...e operation of the device and or system NOTE Risk of electric shock Live parts Shut off the electric supply before opening the HIU cover 1 During installation and maintenance operations always avoid d...

Page 4: ...Dimensions SATK30 A B C kg G B G B G B 16 A B C kg G B G B G B 19 550 A A B B 65 65 450 C C 59 101 160 65 190 195 430 15 490 46 10 245 110 265 110 85 A A B B 629 65 65 550 C C 159 101 160 65 290 195 5...

Page 5: ...changer brazed stainless steel Installation The SATK series HIUs are designed for installation in a sheltered domestic environment or similar therefore cannot be installed or used outdoors i e in area...

Page 6: ...ent Connection to the main supply The device is supplied with an electric supply cable plug not supplied The device should be electrically connected to a 230 V ac single phase earth mains supply using...

Page 7: ...e cover close the isolating valves empty the HIU using the drain cocks provided remove the spacer piece A remove the blanking plug B install the ow probe in the 1 4 pocket B provided install the ow me...

Page 8: ...vated the circulation pump shuts down and the and the regulating valve closes Heating cycle activation is indicated by a ashing fault LED on the electronic controller This fault does not affect the ge...

Page 9: ...d Safety valve fault Error code 76 SATK20103 LOW temperature Removing a fault Normal operating conditions are restored automatically once the faulty safety valve is working correctly again Safety sett...

Page 10: ...tic water preheating function Heating cycle modulating temperature regulation with compensated set point floor slab heating function Factory settings Components SATK20203 MEDIUM Temperature HIU Item C...

Page 11: ...ds the drying of the under oor heating screed at low temperatures This function can only be activated and executed if there are no faults It can be activated by pressing and holding the RESET button f...

Page 12: ...al load under control The thermal response time of the system is thus minimised Safety and alarms Error codes associated with faults signalled by the lighting up of the FAULT LED are also shown on the...

Page 13: ...The function is enabled by setting dip switch 5 to the ON position During periods when the domestic water cycle is not used if the DHW probe detects a temperature 10 C below the SET value the control...

Page 14: ...eturn temperature sensor 22 Pressure gauge 23 Filling loop isolation valve 24 Filling loop double check valve 25 Filling loop Not shown on Components illustration Functional characteristics SATK30103...

Page 15: ...rying of the under oor heating screed at low temperatures This function can only be activated and executed if there are no faults It can be activated by pressing and holding the RESET button for 8 sec...

Page 16: ...l maintenance procedures should be carried out by an authorised technician Regular maintenance guarantees better ef ciency and helps to save energy Before carrying out any maintenance repair or part r...

Page 17: ...the new probe Reconnect the connector respecting the only possible way it can be inserted When carrying out maintenance on the electrical system for the connections follow the diagram on page 16 Afte...

Page 18: ...HW production valve actuator x x x x Thermal safety relief valve x x Thermal safety thermostat x x Heating flow temperature probe x x x x x x x x x x x x x x x Electric supply 230 V ac x x x x x x x x...

Page 19: ...artly clogged call quali ed personnel to have it serviced modulating valve actuator faulty call quali ed personnel to have it replaced valve obturator blocked in intermediate position call quali ed pe...

Page 20: ...valves terminals closed open the valves centralised system temperature insuf cient contact person in charge of system electronic controller not working call quali ed personnel to have it replaced prim...

Reviews: