Fault

Indications

Possible Cause of Fault

Operations to be Performed

The room is not

reaching the desired

temperature

CH led on

heating cycle temperature set point too low

increase set point

chrono-thermostat temperature setting incorrect

check programming of chrono-thermostat

HIU strainer clogged

call qualified personnel to have it serviced

heating valve actuator faulty

call qualified personnel to have it replaced

heating valve obturator blocked

call qualified personnel to have it replaced

modulating valve actuator connector disconnected

restore correct connection

DHW temperature probe cable inverted with heating probe

restore correct connection

presence of air in the system

vent the system

pump (if present) not working

call qualified personnel to have it replaced

pump cable (if present) not connected

restore connection

possible system shut-off valves/terminals closed

open the valves

centralised system temperature insufficient

contact person in charge of system

electronic controller not working

call qualified personnel to have it replaced

primary circuit flow rate insufficient

contact person in charge of system

centralised system not working

contact person in charge of system

CH led off

timer/thermostat time setting incorrect

check programming of timer/thermostat

timer/thermostat not working

check timer/thermostat

all leds are off

electric supply switched off

restore HIU electric supply

protection fuse burnt out

restore HIU electric supply

FAULT led lit + error
code 4 active

heating circuit pressure too low

restore system pressure

FAULT led lit + error

code 5 active

heating temperature probe faulty

call qualified personnel to have it replaced

FAULT led lit + error

code 15 active

compensation temperature probe faulty

call qualified personnel to have it replaced

FAULT led lit + error

code 69 active

safety thermostat cut in

call qualified personnel to have it serviced

FAULT led lit + error
code 76 active

safety relief valve faulty

call qualified personnel to have it serviced

FAULT led lit + error

code 79 active

incorrect switch setting

restore correct switch settings

Fault Finding

Summary of Contents for Altecnic SATK20

Page 1: ...SATK20 SATK30 heat interface unit Installation Operation Maintenance Instructions...

Page 2: ...roduct range 1 Safety instructions 1 Dimensions and technical speci cation 3 Installation 4 First operation 5 Electronic controller 6 Safety and alarms 7 SATK20103 and SATK20203 components 8 SATK20303...

Page 3: ...e operation of the device and or system NOTE Risk of electric shock Live parts Shut off the electric supply before opening the HIU cover 1 During installation and maintenance operations always avoid d...

Page 4: ...Dimensions SATK30 A B C kg G B G B G B 16 A B C kg G B G B G B 19 550 A A B B 65 65 450 C C 59 101 160 65 190 195 430 15 490 46 10 245 110 265 110 85 A A B B 629 65 65 550 C C 159 101 160 65 290 195 5...

Page 5: ...changer brazed stainless steel Installation The SATK series HIUs are designed for installation in a sheltered domestic environment or similar therefore cannot be installed or used outdoors i e in area...

Page 6: ...ent Connection to the main supply The device is supplied with an electric supply cable plug not supplied The device should be electrically connected to a 230 V ac single phase earth mains supply using...

Page 7: ...e cover close the isolating valves empty the HIU using the drain cocks provided remove the spacer piece A remove the blanking plug B install the ow probe in the 1 4 pocket B provided install the ow me...

Page 8: ...vated the circulation pump shuts down and the and the regulating valve closes Heating cycle activation is indicated by a ashing fault LED on the electronic controller This fault does not affect the ge...

Page 9: ...d Safety valve fault Error code 76 SATK20103 LOW temperature Removing a fault Normal operating conditions are restored automatically once the faulty safety valve is working correctly again Safety sett...

Page 10: ...tic water preheating function Heating cycle modulating temperature regulation with compensated set point floor slab heating function Factory settings Components SATK20203 MEDIUM Temperature HIU Item C...

Page 11: ...ds the drying of the under oor heating screed at low temperatures This function can only be activated and executed if there are no faults It can be activated by pressing and holding the RESET button f...

Page 12: ...al load under control The thermal response time of the system is thus minimised Safety and alarms Error codes associated with faults signalled by the lighting up of the FAULT LED are also shown on the...

Page 13: ...The function is enabled by setting dip switch 5 to the ON position During periods when the domestic water cycle is not used if the DHW probe detects a temperature 10 C below the SET value the control...

Page 14: ...eturn temperature sensor 22 Pressure gauge 23 Filling loop isolation valve 24 Filling loop double check valve 25 Filling loop Not shown on Components illustration Functional characteristics SATK30103...

Page 15: ...rying of the under oor heating screed at low temperatures This function can only be activated and executed if there are no faults It can be activated by pressing and holding the RESET button for 8 sec...

Page 16: ...l maintenance procedures should be carried out by an authorised technician Regular maintenance guarantees better ef ciency and helps to save energy Before carrying out any maintenance repair or part r...

Page 17: ...the new probe Reconnect the connector respecting the only possible way it can be inserted When carrying out maintenance on the electrical system for the connections follow the diagram on page 16 Afte...

Page 18: ...HW production valve actuator x x x x Thermal safety relief valve x x Thermal safety thermostat x x Heating flow temperature probe x x x x x x x x x x x x x x x Electric supply 230 V ac x x x x x x x x...

Page 19: ...artly clogged call quali ed personnel to have it serviced modulating valve actuator faulty call quali ed personnel to have it replaced valve obturator blocked in intermediate position call quali ed pe...

Page 20: ...valves terminals closed open the valves centralised system temperature insuf cient contact person in charge of system electronic controller not working call quali ed personnel to have it replaced prim...

Reviews: