SATK20 & SATK30

12

To modify the factory settings and enable the HIU to support
LOW temperature systems (25 to 45˚C), proceed as follows.

1

Switch off the electricity power supply to the HIU

2

Set the switches 2 and 3 with the ON-OFF setting

Operating Cycles SATK20 High Temperature

Heating cycle:  ON/OFF regulation.

When the room thermostat requests the start of a heating
cycle, the valve is opened completely, allowing water to
circulate at the temperature supplied by the central heating
system (ON-OFF regulation).

The valve is closed on completion of the heating cycle.

The active heating cycle is signalled by the yellow CH LED
which comes on.

No value is shown on the display.

Optional functions

- to activate/deactivate the optional

functions the electric power supply must always be turned off.

Domestic water generation

Domestic water pre-heating function

The function is enabled by setting dip switch 5 to the ON
position.

During periods when the domestic water cycle is not used, if
the DHW probe detects a temperature 10˚C below the SET
value, the controller partially opens the domestic water
modulating valve for the time required (max. 5 mins) to bring
the temperature detected up to a value 5˚C below the set point
value.

The domestic water preheating function is signalled by the
flashing yellow DHW LED.

This function is less of a priority than any domestic water or
heating cycles.

Safety and alarms

Error codes associated with faults are signalled by the
illumination of the FAULT LED are also shown on the display
(see page 8).

Operating Cycles SATK20

Factory settings SATL30103 & SATK30105

SATK30103 & SATK30105 are factory set to support HIGH
temperature heating (50 to 75˚C), with the following switch
settings.

Factory settings

3 Remove the safety thermostat jumper cable and 

connect the cables to the thermostat. 

4

Switch on the electricity power supply to the HIU.

5

ON

48

4

––

1

2

3

4

5

6

4

ON

1

2

3

4

5

6

4

ON

Summary of Contents for Altecnic SATK20

Page 1: ...SATK20 SATK30 heat interface unit Installation Operation Maintenance Instructions...

Page 2: ...roduct range 1 Safety instructions 1 Dimensions and technical speci cation 3 Installation 4 First operation 5 Electronic controller 6 Safety and alarms 7 SATK20103 and SATK20203 components 8 SATK20303...

Page 3: ...e operation of the device and or system NOTE Risk of electric shock Live parts Shut off the electric supply before opening the HIU cover 1 During installation and maintenance operations always avoid d...

Page 4: ...Dimensions SATK30 A B C kg G B G B G B 16 A B C kg G B G B G B 19 550 A A B B 65 65 450 C C 59 101 160 65 190 195 430 15 490 46 10 245 110 265 110 85 A A B B 629 65 65 550 C C 159 101 160 65 290 195 5...

Page 5: ...changer brazed stainless steel Installation The SATK series HIUs are designed for installation in a sheltered domestic environment or similar therefore cannot be installed or used outdoors i e in area...

Page 6: ...ent Connection to the main supply The device is supplied with an electric supply cable plug not supplied The device should be electrically connected to a 230 V ac single phase earth mains supply using...

Page 7: ...e cover close the isolating valves empty the HIU using the drain cocks provided remove the spacer piece A remove the blanking plug B install the ow probe in the 1 4 pocket B provided install the ow me...

Page 8: ...vated the circulation pump shuts down and the and the regulating valve closes Heating cycle activation is indicated by a ashing fault LED on the electronic controller This fault does not affect the ge...

Page 9: ...d Safety valve fault Error code 76 SATK20103 LOW temperature Removing a fault Normal operating conditions are restored automatically once the faulty safety valve is working correctly again Safety sett...

Page 10: ...tic water preheating function Heating cycle modulating temperature regulation with compensated set point floor slab heating function Factory settings Components SATK20203 MEDIUM Temperature HIU Item C...

Page 11: ...ds the drying of the under oor heating screed at low temperatures This function can only be activated and executed if there are no faults It can be activated by pressing and holding the RESET button f...

Page 12: ...al load under control The thermal response time of the system is thus minimised Safety and alarms Error codes associated with faults signalled by the lighting up of the FAULT LED are also shown on the...

Page 13: ...The function is enabled by setting dip switch 5 to the ON position During periods when the domestic water cycle is not used if the DHW probe detects a temperature 10 C below the SET value the control...

Page 14: ...eturn temperature sensor 22 Pressure gauge 23 Filling loop isolation valve 24 Filling loop double check valve 25 Filling loop Not shown on Components illustration Functional characteristics SATK30103...

Page 15: ...rying of the under oor heating screed at low temperatures This function can only be activated and executed if there are no faults It can be activated by pressing and holding the RESET button for 8 sec...

Page 16: ...l maintenance procedures should be carried out by an authorised technician Regular maintenance guarantees better ef ciency and helps to save energy Before carrying out any maintenance repair or part r...

Page 17: ...the new probe Reconnect the connector respecting the only possible way it can be inserted When carrying out maintenance on the electrical system for the connections follow the diagram on page 16 Afte...

Page 18: ...HW production valve actuator x x x x Thermal safety relief valve x x Thermal safety thermostat x x Heating flow temperature probe x x x x x x x x x x x x x x x Electric supply 230 V ac x x x x x x x x...

Page 19: ...artly clogged call quali ed personnel to have it serviced modulating valve actuator faulty call quali ed personnel to have it replaced valve obturator blocked in intermediate position call quali ed pe...

Page 20: ...valves terminals closed open the valves centralised system temperature insuf cient contact person in charge of system electronic controller not working call quali ed personnel to have it replaced prim...

Reviews: