SATK20 & SATK30

8

Compensation probe fault - Error code: 15
SATK20103 - LOW temperature
SATK30103 - at LOW temperature setting

Domestic water probe fault - Error code: 6

Safety thermostat cutout - Error code: 69
SATK20103 - LOW temperature
SATK30103 - at LOW temperature setting

Removing a fault

Once the correct pressure has been achieved on the heating
circuit, the fault can be reset. (see page 7).

Probe fault

If the domestic water temperature probe fails, domestic water
generation will cease immediately. Heating performance will
not be affected. 

If the heating probe fails, the heating will cease immediately.
The domestic water generation will not be affected. The probe
fault is indicated by a flashing fault LED on the electronic
controller.

Heating probe fault - Error code: 5

After the user has reset the isolation imposed by the safety
thermostat, the shut-off valve can only be re-enabled when
the mixing/modulating valves are completely closed again.

This means that if a domestic water cycle is in progress, the
activation of the shut-off valve will be postponed until the
end of that domestic water cycle.

Removing a fault

Before resetting the controller, the manual
reset button will need to be pressed.

Safety valve fault - Error code: 76
SATK20103 - LOW temperature

Removing a fault

Normal operating conditions are restored automatically once
the faulty safety valve is working correctly again.

Safety setting incorrect - Error code: 76

Removing a fault

Normal operation will be restored once the probe is replaced.
(see page 15).

Removing a fault

Restore correct switch setting according to Table 1

Automatic controller function

Rese  t mixing/modulating valve to zero

Immediately after the power supply has been switched on,
the position of the mixing/modulating valves is reset to zero.

Pump anti-clog

When the pump is not in use, it is powered on for a period of
5 seconds every 24 hours.

Mixing valve/modulating valve anti-clog

The anti-clogging cycle for the mixing/modulating valve is run
every 24 hours.

The HIU is configured to support low temperature heating
(low temperature models only), constantly monitors the
heating flow temperature and includes a safety thermostat. 

If the thermostat is activated during a general cycle, the
circulation pump will immediately stop, the mixing valve and
safety lock valve (SATK20103) will close. Safety thermostat
activation is indicated by a steady, red fault LED on the
electronic controller. This fault locks all functions.

In the event of a power failure, the thermal safety valve
prevents hot water for heating purposes from entering the
system.

15

5

6

76

79

69

Summary of Contents for Altecnic SATK20

Page 1: ...SATK20 SATK30 heat interface unit Installation Operation Maintenance Instructions...

Page 2: ...roduct range 1 Safety instructions 1 Dimensions and technical speci cation 3 Installation 4 First operation 5 Electronic controller 6 Safety and alarms 7 SATK20103 and SATK20203 components 8 SATK20303...

Page 3: ...e operation of the device and or system NOTE Risk of electric shock Live parts Shut off the electric supply before opening the HIU cover 1 During installation and maintenance operations always avoid d...

Page 4: ...Dimensions SATK30 A B C kg G B G B G B 16 A B C kg G B G B G B 19 550 A A B B 65 65 450 C C 59 101 160 65 190 195 430 15 490 46 10 245 110 265 110 85 A A B B 629 65 65 550 C C 159 101 160 65 290 195 5...

Page 5: ...changer brazed stainless steel Installation The SATK series HIUs are designed for installation in a sheltered domestic environment or similar therefore cannot be installed or used outdoors i e in area...

Page 6: ...ent Connection to the main supply The device is supplied with an electric supply cable plug not supplied The device should be electrically connected to a 230 V ac single phase earth mains supply using...

Page 7: ...e cover close the isolating valves empty the HIU using the drain cocks provided remove the spacer piece A remove the blanking plug B install the ow probe in the 1 4 pocket B provided install the ow me...

Page 8: ...vated the circulation pump shuts down and the and the regulating valve closes Heating cycle activation is indicated by a ashing fault LED on the electronic controller This fault does not affect the ge...

Page 9: ...d Safety valve fault Error code 76 SATK20103 LOW temperature Removing a fault Normal operating conditions are restored automatically once the faulty safety valve is working correctly again Safety sett...

Page 10: ...tic water preheating function Heating cycle modulating temperature regulation with compensated set point floor slab heating function Factory settings Components SATK20203 MEDIUM Temperature HIU Item C...

Page 11: ...ds the drying of the under oor heating screed at low temperatures This function can only be activated and executed if there are no faults It can be activated by pressing and holding the RESET button f...

Page 12: ...al load under control The thermal response time of the system is thus minimised Safety and alarms Error codes associated with faults signalled by the lighting up of the FAULT LED are also shown on the...

Page 13: ...The function is enabled by setting dip switch 5 to the ON position During periods when the domestic water cycle is not used if the DHW probe detects a temperature 10 C below the SET value the control...

Page 14: ...eturn temperature sensor 22 Pressure gauge 23 Filling loop isolation valve 24 Filling loop double check valve 25 Filling loop Not shown on Components illustration Functional characteristics SATK30103...

Page 15: ...rying of the under oor heating screed at low temperatures This function can only be activated and executed if there are no faults It can be activated by pressing and holding the RESET button for 8 sec...

Page 16: ...l maintenance procedures should be carried out by an authorised technician Regular maintenance guarantees better ef ciency and helps to save energy Before carrying out any maintenance repair or part r...

Page 17: ...the new probe Reconnect the connector respecting the only possible way it can be inserted When carrying out maintenance on the electrical system for the connections follow the diagram on page 16 Afte...

Page 18: ...HW production valve actuator x x x x Thermal safety relief valve x x Thermal safety thermostat x x Heating flow temperature probe x x x x x x x x x x x x x x x Electric supply 230 V ac x x x x x x x x...

Page 19: ...artly clogged call quali ed personnel to have it serviced modulating valve actuator faulty call quali ed personnel to have it replaced valve obturator blocked in intermediate position call quali ed pe...

Page 20: ...valves terminals closed open the valves centralised system temperature insuf cient contact person in charge of system electronic controller not working call quali ed personnel to have it replaced prim...