FREETIME
® -
HEXAMOTION
®
High Efficiency Recovery Unit
OPERATING AND COMMISSIONING INSTRUCTIONS
MS-CDF-010
Ind F
Maj. 18/05/2017
Créé par : JC
Validé par : AR
Page 19/57
*A raccorder directement sur régulateur CORRIGO
** A raccorder directement sur régulateur CORRIGO et 8A max sur l’ensemble des DO
BC
15-16-17
BC :Connect to 3 ways valve of the hot water battery (cf chapter IV.12)
BE
18 + DO3**
BE : Connect to static contactor of the electric battery (see chapter IV.14)
Heating pump
(PREMIUM BC)
18 + DO3**
Connect to hot water circulator (Note : 24V 2AMax to relay) (see chapter IV.12)
Cooling pump
19 + DO4**
Connect to cold water circulator (Note : 24V 2AMax to relay)(see chapter IV.12)
AL
20 + DO5**
24V output available if unit is in default (Note : 24V 2A Max to relay)
NC (Night cooling)
(LOBBY
®
)
22 + DO7**
24V output available if unit runs with the optional LOBBY EC for opening
dampers during Night Cooling. (pay attention : 24V 2A Max to relay)
TRPS
23 / Agnd* + UI1* Connect to supply Pressure Transmitter (see chapter IV.8)
DEPS
24 + UI1*
Connect to terminal 1 and 3 of supply pressure switch (see chapter IV.7)
TRPR
25 / Agnd* + UI2* Connect to return pressure Transmitter (see chapter IV.8)
DEPR
26 + UI2*
Connect to terminal 1 and 3 of return pressure switch (see chapter IV.7)
CO2
27 / Agnd* UI3*
Connect to CO2 sensor (see chapter IV.10) DIVA/QUATTRO option
BF
28-29-30
BF :Connect to 3 ways valve of the cold water battery (see chapter IV.12)
DEP FS
DEP FR
31-32
33-34
Connect to terminal of exhaust filter switch (see chapter IV.6)
Connect to terminal 1 and 3 of return filter switch (see chapter IV.6)
RMS
35 + DO1**
Connect to fresh air damper actuator
RMR
36 + DO2**
Connect to extract air damper actuator
ROUE
37-38 and 21-22
Rotative exchanger wiring (Cf IV.5)
0-10V S
39-40
Connect to Supply air fan (cf chapter VIII.2 and 5)
0-10V R
41-42
Connect to Extract air fan (cf chapter VIII.2 and 5)