V.3.b. Temperature menu
V.3.c. Ventilation menu
Ventilation
Frequency control
(ECO OU DIVA)
SAF
Output: 70 (5)
%
or
Pressure Control EAF
(LOBBY)
Real : 183Pa (exemple)
Setpoint : 180 Pa(5)
Frequency control
manuel vent.SAF
Output 1/1: 70% (5)
Output 1/2: 50% (5)
(5)
Speeds, pressures, airflows (see chapter V.4.b)
Frequency control
manuel vent.EAF
Output 1/1: 180Pa (5)
Output 1/2: 180Pa (5)
Frequency control
(ECO OU DIVA)
manuel vent.SAF
Output: 70 (5)
%
or
Pressure Control EAF
(LOBBY)
Real : 183Pa (exemple)
Setpoint : 180 Pa(5)
Frequency control
manuel vent.SAF
Output 1/1: 70% (5)
Output 1/2: 50% (5)
Frequency control
manuel vent.EAF
Output 1/1: 180Pa (5)
Output 1/2: 180Pa (5)
Temperature.
Extarct Temperature
Real:
Setpoint : 21°C (8)
Setpoint comp ext
-20°C = 25°C (8)
-15°C = 24°C (8)
-10°C = 23°C (8)
(8)
Temperature setpoint setting (see chapter V.4.c)
Outdoor temp :
Supply temp
Real :
Cons
Setpoint :
Consigne comp ext
-5°C = 23°C (8)
0°C = 22°C (8)
5°C = 20°C (8)
Setpoint comp ext
10°C = 18°C (8)
15°C = 18°C (8)